ID-E270-011GB
67
3
0 ÷ 31
0 ÷ 1024 ‘conjunction’ of 1
st
stage alarms in assigned zones
4
0
―
general 2
nd
stage alarm
5
0 ÷ 31
0 ÷ 1024 ‘union’ of 2
nd
stage alarms in assigned zones
6
0 ÷ 31
0 ÷ 1024 ‘conjunction’ of 2
nd
stage alarms in assigned zones
Variant 0
Means lack of an actuation criterion (permanently non-activated output).
Variant 1 – general 1st stage alarm
The output activation is performed in the case of a 1
st
stage alarm occurrence in the control panel or
any control panels of the common supervision area.
Variant 2 – ‘union’ of 1
st
stage alarms in assigned zones of the common supervision area control
panels
The output activation is performed in the case of a 1
st
stage alarm occurrence in at least one zone
that is assigned to this relay.
Variant 3 – ‘conjunction’ of 1
st
stage alarms in assigned zones of common supervision area control
panels
The output activation is performed in the case of a 1
st
stage alarm occurrence in at least two zones
that are assigned to this relay.
Variant 4 – general 2
nd
stage alarm
The output activation is performed in the case of a 2
nd
stage alarm occurrence in the control panel or
any control panels of the common supervision area.
Variant 5 – ‘union’ of 2
nd
stage alarms in assigned zones of the common supervision area control
panels
The output activation is performed in the case of a 2
nd
stage alarm occurrence in at least one zone
that is assigned to this relay.
Variant 6 – ‘conjunction’ of 2
nd
stage alarms in assigned zones of common supervision area control
panels
The output activation is performed in the case of a 2
nd
stage alarm occurrence in at least two zones
that are assigned to this relay.
In the case of variant 2 and variant 5 application, at least one zone should be assigned to an UCS,
whereas in the case of variant 3 and variant 6 application, at least two zones should be assigned.
Variants 1 and 4 do not require any zone assignation.
In the case of variants with zone dependence, the assigned zones are allocated to own control panel
(an alone panel) or to control panels of the common supervision area (panels operating in a
network).
The total number of zones assignments to all executive outputs and SAL type elements in the control
panel should not exceed 64,000.
Note:
A non-maskable fault is also not signalled if the output is settled at variant 0.