control panel. After the output is actuated (according to a proper actuation variant), the output
voltage polarisation is positive.
Specifications of the PK supervised relay output lines
The relay outputs can be supervised, in the control panel quiescent mode, in case the PPW-49
module is applied and in the control panel outputs supervision is declared. The output lines should
be connected pursuantly to Fig. 5.7. The quiescent current lower than 1.2 mA flows in a line
connected in such a manner. In the case the current flow is undesirable (e.g. load activation occurs),
it is necessary to disconnect the supervision circuit by placing an appropriate jumper in the 1-2
position (Fig. 5.6) and undeclaring the output supervision in the control panel.
Output actuation criteria for control panel network version
In Tables 5.4 ÷ 5.8 presenting the programming possibilities of the PK and LS outputs, the "control
panels’ numbers" parameter (for control panels operating within a network) has the following
meaning:
I. For variants without additional zone dependencies:
•
control panel number = 0 means the dependence on an occurrence in any control panel
included in the common detection area;
•
control panel number > 0 means the dependence on an occurrence in a given control panel
(provided it is included in the common detection area);
•
control panel number ”―” allows for making actuation dependent only on local control panel
occurrences.
II. For variants with additional zone dependencies:
•
control panel number = 0 means the dependence on the total number of occurrences in
selected zones in any control panel included in the common detection area;
•
control panel number > 0 means the dependence on the ‘union’ of occurrences in selected
zones of given control panels (provided they are included in the common detection area);
•
control panel number ”―” allows for making actua]on dependent only on local control panel
occurrences.
Notes:
1. "Zone 0" means the dependence on the ‘union’ of occurrences from all zones supported by a given
control panel.
2. "The union of occurrences" means that an actuation criterion is fulfilled if at least one occurrence
happens.
3. The total number of zones, EKS and EWK elements assigned to all executive outputs and SAL type
elements in the control panel must not exceed 64,000.