ID-E270-011GB
51
-
an element number (1 ÷ 127) using the automatic configuration or configuration with
verification or manual configuration procedures;
-
a logical number (1 ÷ 250);
-
an operation mode (it is set by default but may be changed – see below).
The EKS-4001 operation mode is defined by the following element parameters (standard mode in
bold print):
-
output line continuity monitoring (
YES
or NO);
-
input 1 - actuation monitoring (YES (40 sec.) or YES (70 sec.) or YES (130 sec.) or
NO
);
-
input 2 - actuation monitoring (YES (40 sec.) or YES (70 sec.) or YES (130 sec.) or
NO
);
-
input 1 operation method (NC or
NO
);
-
input 2 operation method (NC or
NO
);
-
output relay actuation delay.
The set of parameters defining an operation mode is directly connected with a line element and is
programmed while declaring the EKS element as a line element. An operation mode may always be
changed in the program.
Stage II:
The EKS-4001 logical configuration consisting in assigning:
-
a variant to the previously assigned logical number;
-
a set of assigned zones if it is required by a given variant (from the 1 ÷ 1024 range; from own
control panel or control panels of a common detection area);
-
a set of assigned inputs of other EKS elements if it is required by a given variant (or own
inputs if the variant permits it) – range of assigned EKS elements: 1 ÷ 250, EKS inputs range:
1 ÷ 2 – only of own control panel);
-
a set of assigned EWK inputs if it is required by a given variant (range of assigned EWK
elements: 1 ÷ 100, EWK inputs range: 1 ÷ 8 – only of own control panel);
-
user messages for a technical alarm and non-maskable fault of monitoring inputs.
The EKS-4001 output relay activation variants
Table 7.1 lists the EKS output programming possibilities. The "control panel number" parameter (only
for control panels operating in a network) has the following meaning:
-
control panel number = 0 shows the dependence on an event in any control panel included in
the common detection area;
-
control panel number > 0 shows the dependence on an event from a given control panel
(provided it is included in the common detection area);
-
control panel number ”―” allows for actua]on dependence only on local control panel
events.
For variants with additional zone dependencies: zone number = 0 shows the dependence on the
‘union’ of events within all zones in a selected control panel included in the common detection area.