ID-E270-011GB
63
-
modes of an addressable module for communication with the POLON 4000 system:
o
EEPROM memory fault;
o
short circuit isolator actuation;
o
shot circuit isolation;
o
no connection between the line processor and main UCS element.
Depending on whether the programmed variant condition is met, the POLON 4900 control panel may
send a signal actuating the P1 main relay to the UCS (and other outputs individually dependent on
this signal).
The UCS controlling panel configuration may be programmed by means of keys located in this unit,
however, the data regarding the co-operation of the UCS with a fire detecting control panel must be
declared in the POLON 4900 control panel.
The UCS proper programming consists in declaring a line element (similarly to fire warning devices)
and assigning it to a logical number.
A logical number for UCS is selected from the 1 ÷ 100 range and assigned to an element in order to
make the UCS actuation variants dependent on different events in its own control panel or control
panels in the common detection area and provide it with the required user messages. Each UCS type
element may be assigned only to one logical number and vice versa.
The UCS 4000 operation results from the P1 main relay actuation variant and individual setting for
keys in UCS 4000.
A full UCS 4000 programming procedure in the POLON 4900 includes two stages:
Stage I:
UCS 4000 declaration consisting in assigning:
-
an element number (1 ÷ 127) using the automatic configuration or the configuration with
verification or the manual configuration procedures;
-
a logical number (1 ÷ 100).
Stage II:
UCS 4000 logical configuration consisting in assigning:
-
a P1 main relay actuation variant to a previously assigned logical number;
-
fire alarm zone (1 ÷ 1024) or zone 0 to block the reception of a fire alarm from the UCS unit;
user messages for a technical alarm and non-maskable fault of outputs: P1 main relay and P2/P3
additional relays.
The P1 main relay actuation variants for the UCS 4000 control panel
See Table 7.5 for the possibilities of activating the P1 main relay for the UCS 4000 control panel. The
"control panel number" parameter (only for control panels operating in a network) has the following
meaning:
-
control panel number = 0 shows the dependence on an event in any control panel included in
the common detection area;
-
control panel number > 0 shows the dependence on an event from a given control panel
(provided it is included in the common detection area);
-
control panel number ”―” allows for making actua]on dependent only on local control panel
events.
For variants with additional zone dependencies: zone number = 0 shows the dependence on the total
number of events within all zones in a selected control panel included in the common detection area.