ID-E270-011GB
87
-
TEST indicator – global testing mode for the control panels of the common detection area;
the push button enables display of all control panel tests and general information regarding
the test occurrences in the control panels within the common detection area. In order to
view the fault tests within the remote control panel in detail, select the remote control panel
and view its tests.
-
TECHNICAL ALARM indicator – global technical alarm mode for the control panels of the
common detection area; the push button enables display of all control panel technical alarms
and general information regarding the technical alarm occurrences in the control panels
within the common detection area. In order to view the technical alarms within the remote
control panel in detail, select the remote control panel and view its technical alarms.
-
ACKNOWLEDGEMENT indicator – global mode of the indicator for the control panels of the
common detection area; the push button enables acknowledgement of all events in the
control panels within the common detection area.
-
RESET indicator – shows the possibility of cancelling a local control panel alarm or locally
received alarm from the control panels of the detection area; the push button resets an
alarm in the control panels within the common detection area.
-
Other indicators, i.e. PERSONNEL ABSENT, DELAYS OFF, POWER SUPPLY, ALARM DEVICES and
ALARM TRANSMISSION DEVICES, show the local control panel mode.
In order to view the events in a remote control panel, select this panel and proceed similarly to
viewing the events in a local control panel.
In the collective mode, if a remote control panel is declared for co-operation as one of the control
panels within the common detection area, even after disabling the remote operation in this control
panel, it is still possible to remotely operate the ACKNOWLEDGEMENT and RESET push buttons.
In the collective mode, all programming, disablement, testing and programming review functions
relate to the control panel with the local number.
9.2.3 Remote mode
In the remote mode, it is possible to select access to any "remote" control panel (also outside the
common detection area) and view its software resources and condition (i.e. faults, disablements,
event memory, etc.).
In the remote mode, when the number of a different control panel is selected, the remote control
panel mode is displayed on the operator's panel. All readout and configuration functions relate to
the remote control panel. In this mode, the real condition of the remote control panel is displayed
without displaying the common (collective) condition of a distant control panel. For example, if an
alarm from a different control panel within the common detection area is generated in the remote
control panel, detection is remotely visible in this control panel since no zones belonging to this
control panel is in the alarm mode.
The possibility of changing the condition and modifying the configuration resources in the remote
control panel depends on the remote operation option programmed in this panel.
Three levels of remote access to a remote control panel may be programmed in this panel. They
correspond to the access levels in a local control panel. The 4
th
level is remotely forbidden (disabled).
The remote access may be disabled (recommended) but it does not mean that the access is fully
denied to this control panel as its condition and software resources may still be reviewed.
After selecting a "remote" control panel, the indicators of "our" local control panel show the mode of
the indicators installed in the former. The possibility of using the operating push buttons (in order to
change its mode) depends on the provided level of "remote operation" in the remote control panel.