60
ID-E270-011GB
Type1
Table 7.3
Variant
Control
Panels
No.
Zones
Numbers
Time
Parameters
Actuation Criterion
1
0
―
T3
1
st
stage alarm in control panel (or control panel group
in case of network operation) or activation with
ACTIVATION push button in ALARM DEVICES area
2
0 ÷ 31
0 ÷ 1024
T3
1
st
stage alarm in assigned zones
Note:
The countdown of the delay time will be discontinued (T3 time will be reset during the countdown
time) and the outputs to alarm devices will be activated immediately after the control panel enters
the 2
nd
stage alarm mode. After setting the T3 parameter to maximum time (10 minutes), the
actuation criterion may be dependent on "the 2
nd
stage alarm only".
Type 3
Table 7.4
Variant
Control
Panels
No.
Zones
Numbers
Time
Parameters
Actuation Criterion
1
0
―
T
op
1
st
stage alarm in control panel
2
0
―
T
op
1
st
stage alarm in control panel until acknowledgement
3
0
―
T
op
2
nd
stage alarm in control panel
4
0
―
T
op
2
nd
stage alarm in control panel until acknowledgement
5
0 ÷ 31
0 ÷ 1024
T
op
1
st
stage alarm in assigned zones
6
0 ÷ 31
0 ÷ 1024
T
op
1
st
stage alarm in assigned zones until acknowledgement
7
0 ÷ 31
0 ÷ 1024
T
op
2
nd
stage alarm in assigned zones
8
0 ÷ 31
0 ÷ 1024
T
op
2
nd
stage alarm in assigned zones until acknowledgement