Ambient temperature should not be lower than 0 °C and higher than + 40 °C. In the case of high noise
level, outdoor acoustic signalling devices should be applicable, controlled by signalling line or the
relay contacts.
The control panel should be fixed to a wall using a special supporting frame delivered with the
device.
In the control panel vicinity (within sight) a manual fire call point should be installed.
Fig. 12.2 PAR-4800 battery container fixing
Note:
The disposable pattern delivered with the control panel should be used for mounting hole drilling.
12.2 POWER SUPPLY CONNECTION
Three clamps (located on the back wall together with an anti-distortion filter are provided to connect
mains cables that supply the control panel. The mains clamps are covered with a special isolation
shield with ~230 V/50 Hz description. The supplying cable marking is provided on appropriate
clamps. The cables should be connected to the proper clamps in accordance with their dedication.
The reserve power supply (batteries) should be connected after the mains power supply connection.