ID-E270-011GB
65
The P1 main relay actuation variants are programmed only for a UCS unit with a logical number
defined.
In case variant 2 or 5 is used, at least one zone must be assigned to the UCS, however, if variant 3
or 6 is used, at least two zones must be assigned. Variants 1 and 4 do not require assigning any
zones.
As far as the variants with zone dependence are concerned, the assigned zones may originate in
their own control panel (a standalone control panel) or in any control panels from the common
detection area (a control panel operating in a network).
The total number of zone assignments to all executive outputs and SAL type elements in the
control panel must not exceed 64,000.
Note:
-
A non-maskable fault will not be signalled if variant 0 is set for an output.
-
After completing the standard and automatic configuration procedures, the UCS type
elements are assigned to a special logical number 0 which makes them inactive.
An exemplary drawing showing the UCS 4000 panel use is included in the UCS 4000 I&MM.
7.9 UCS 6000 UNIVERSAL CONTROL PANELS DECLARATION
The UCS 6000 (UCS in short) universal control panel is a standalone device making it possible to
control and supervise fire protection devices, e.g. smoke exhaust dampers, doors, etc. (see the
detailed description provided in its Operation and Maintenance Manual). The UCS controlling panel
may co-operate with the POLON 4900 control panel through a detection line (connected to the
circuit similarly to any other line elements).
The POLON 4900 control panel may receive the following modes from the UCS 6000:
1.
quiescent (also during operation of the air venting function in the UCS);
2.
fire alarm (manual call point active - manual smoke exhaust button connected to a dedicated
UCS input, alarm from a conventional detection line connected to UCS or alarm from an
external input);
3.
technical alarm – acknowledgement of output actuation in the UCS transformed into a fire
alarm from the control panel;
4.
non-maskable fault – lack of actuation of an output in the UCS during a given period of time
transformed into a fire alarm in the control panel;
5.
UCS fault.
The UCS controlling panel full configuration is performed by means of dedicated software.
See the detailed description provided in the product Operation and Maintenance Manual.
The UCS proper programming in the POLON 4900 control panel consists in declaring a line element
(similarly to fire warning devices) and assigning it to a logical number.
A logical number for UCS is selected from the 1 ÷ 100 range and assigned to an element in order to
declare and configure individual modules of the UCS 6000 control panel.
The UCS 6000 entire programming procedure in the POLON 4900 panel includes two stages:
Stage I:
UCS 6000 declaration consisting in assigning:
-
an element number (1 ÷ 127) using the automatic configuration or the configuration with
verification or the manual configuration procedures;