Assembly & Operation Manual
5.6 Settings of output signals
5.6.1 Relay outputs
OUT1 – OUT4
The controller is equipped with four relay outputs
OUT1 – OUT4
. Connection to the
outputs is performed via
XT6 – XT9
connecting blocks of the controller bottom board.
Every output has a complex group of contacts: normally open
NO
, normally closed
NC
and
common output
C
.
Outputs may be used for (Figure 3):
OUT1:
o
as a control output of operation unit OD #1;
OUT2, OUT3,
OUT4:
o
as a control output of OD #2, OD #3 and OD #4,
o
as outputs to control optional equipment (OUT #2
,
OUT #3
,
OUT #4).
Characteristics of output signals:
Maximum commutating voltage of direct current ......................................... max. 30 V
Maximum commutating voltage of alternate current .................................... max. 42 V
Maximum commutated direct/alternate current for outputs Out ..................... max. 5 A
Resistance of closed contact .............................................................. max. 0.15 Ohm
Control outputs support potential and pulse operation modes of OD. Selection of mode is
performed with
Operation mode of control output
parameter of OD
.
In
potential
mode of OD:
In case of single passage relay output is activated for a period of time, set in
software by
Unlocked state holding time
software parameter or till the moment of
passage
.
In case OD is set into
“Open”
mode relay output is activated till the mode change.
In
pulse
mode of OD:
In case of single passage relay output is activated for a period of time, set by
Control
pulse duration
parameter of OD
.
In such case OD remains unlocked until
the passage is performed.
In case OD is set into
“Open”
mode output is activated for a period of time, set by
Control
pulse duration
parameter of OD, and after that it will be activated each
time for the same period in one second after the normalization of OD.
Activation of inputs
IN1 – IN4
, configured as door sensor or signal PASS, define that the
passage was performed in the set direction
.
5.6.2 Outputs
OK1
and
OK2
The controller is equipped with two outputs “open collector”:
OK1
and
OK2
(in
configuration OUT #5 and OUT #6, Figure 3). Connection to the outputs is carried out via
XT3
connecting block of the controller bottom board.
+12VDC supply is derived to the same connecting block for easy connection.
Outputs can be used for following functions:
connection of light and sound alarm devices,
sending of alarm notifications to central surveillance panel,
connection of other optional equipment.
Characteristics of output signals:
Maximum commutation voltage of direct current ...........................................max. 30 V
Maximum commutated current ...................................................................max. 0.25 A
14
Summary of Contents for CT/L-04.2
Page 1: ...Controller CT L 04 2 ASSEMBLY AND OPERATION MANUAL...
Page 2: ...Controller CT L 04 2 Assembly Operation Manual...
Page 22: ...CT L 04 2 Controller Figure 3 Common scheme of connections 21...
Page 26: ...CT L 04 2 Controller Figure 6 Connection schemes of Turnstile control configuration 25...
Page 32: ...CT L 04 2 Controller Figure 13 Connection scheme of optional equipment to controller inputs 31...
Page 44: ...CT L 04 2 Controller Figure 15 Scheme of connection of the card capture reader IC 02 1 43...
Page 45: ...Assembly Operation Manual Figure 16 Scheme of connection of the card capture reader IC 05 44...
Page 70: ...www perco com...