Assembly & Operation Manual
3.
Malfunctions of the computer
(software, databases etc.).
To detect this malfunction, start the command:
ping x.x.x.x
where
x.x.x.x
is the IP-address of the controller.
If there is a communication, you will see lines similar to the following:
Reply from x.x.x.x: bytes=32 time<10ms TTL=128
If there is no communication (response), check routing Settings of your network.
4.
Malfunctions of equipment of Ethernet network
, installed between the computer
and the controller: hub, switch and other network equipment including communication
cables.
To detect this malfunction, start the command:
ping x.x.x.x -l 576
where
x.x.x.x
is the IP-address of the controller.
If there is a communication and standard minimal packets (576 bytes) are not
fragmented, you will see lines similar to the following:
Reply from x.x.x.x: bytes=576 time<10ms TTL=128
In such case IP-packets are not fragmented to the size less than 576 bytes and the
selected connection should be operative.
If the positive answer is not received, the problem might be with network switching
equipment that fragments IP-packets to the size less than 576 bytes. Check settings of
this equipment, enlarge the size of
MTU
. This parameter is usually specified as
MaxMTU
or
IPMTU
.
5.
If several variants of switching are possible
, use command:
ping x.x.x.x -l 576 -t
By switching with various variants, look at response time and choose the connection
with the fastest response.
6.
Malfunctions of the controller.
Failure of elements providing connection via
Ethernet
interface
(IEEE 802.3)
.
To detect this malfunction, have a look at two indicators, installed
8P8C
(
RJ45)
connector of
Ethernet
connection:
LINK
– connection:
o
Green light is on – the controller detects connection to
Ethernet
network,
o
Green light is off – the controller does not detect connection to
Ethernet
network;
ACT
– data exchange
o
Yellow light is blinking – the controller detects data exchange via
Ethernet
network,
o
Yellow light is off – the controller does not detect data exchange via
Ethernet
network.
If the controller does not detect connection to
Ethernet
network (light indicators are off),
connect it to the cable that connects the other controller or computer.
If the controller still does not detect connection to
Ethernet
network or the communication
is not reestablished, contact
PERCo
service in order to repair this controller.
38
Summary of Contents for CT/L-04.2
Page 1: ...Controller CT L 04 2 ASSEMBLY AND OPERATION MANUAL...
Page 2: ...Controller CT L 04 2 Assembly Operation Manual...
Page 22: ...CT L 04 2 Controller Figure 3 Common scheme of connections 21...
Page 26: ...CT L 04 2 Controller Figure 6 Connection schemes of Turnstile control configuration 25...
Page 32: ...CT L 04 2 Controller Figure 13 Connection scheme of optional equipment to controller inputs 31...
Page 44: ...CT L 04 2 Controller Figure 15 Scheme of connection of the card capture reader IC 02 1 43...
Page 45: ...Assembly Operation Manual Figure 16 Scheme of connection of the card capture reader IC 05 44...
Page 70: ...www perco com...