Indication
Probable Cause
Network Status
Off
Device is not on line:
- Device has not completed
dup_MAC-id test.
- Device not powered
- check module status indicator.
Flashing Green
Device is on line but has no
connections in the established state.
Green
Device is on line and has connections
in the established state.
Flashing Red
One or more I/O connections in
timed-out state.
Red
Critical link failure - failed
communication device. Device
detected error that prevents it from
communicating on the network.
Flashing Red/Green Communication faulted device - the
device has detected a network access
error and is in communication faulted
state. Device has received and accepted
an Identity Communication Faulted
Request - long protocol message.
Indication
Probable Cause
I/O Status
Off
Input is in the off state
Yellow
Input on
If your RSLogic 5000 is Version 13.X:
• Choose the equivalent Rockwell Automation module from the list
of modules.
H Series Fieldbus
Modules
Equivalent Rockwell Automation
1738 ArmorPoint Modules
PSSN8M8A
1738-IB8M8
PSSN8M12A
1738-IB8M12
PSSN8M23A
1738-IB8M23
PSSP8M8A
1738-IV8M8
PSSP8M12A
1738-IV8M12
PSSP8M23A
1738-IV8M23
PSSN16M12A
1738-1B16DM12A
•
Enter a name (optional), slot number, and communication format.
Make sure to choose
Compatible Module for Electronic Keying
setting.
• Choose
Next to set RPI.
• Choose
Finish. Notice that the input module is now under the
I/O configuration
H Series Fieldbus 24 VDC Input Modules, Series A
E106P
7
Troubleshoot With the Indicators
MOD
NET
PSSN8M12A
24V dc In
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
PSSN8M12A
I/O Status Indicators
Module Status Indicator
Network Status Indicator
Indication
Probable Cause
Module Status
Off
No power applied to device
Green
Device operating normally
Flashing Green
Device needs commissioning due
to missing, incomplete, or incorrect
configuration
Flashing Red
Recoverable fault
Red
Unrecoverable fault -
may require device replacement
Flashing Red/Green Device is in self-test
Summary of Contents for H Series
Page 135: ...DeviceNet Media Design and Installation Guide...
Page 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Page 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Page 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Page 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Page 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Page 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Page 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Page 263: ......
Page 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Page 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...