EtherNet/IP Adapter - PSSCENA
Expansion I/O Capacity
• Maximum of 63 modules
• Maximum of 5 Rack Optimized connections (for digital modules only)
• Maximum of 25 Direct connections
•
PSSCENA backplane current output = 1.0A maximum. The actual number of modules
can vary. Add up the current requirements of the modules you want to use to make sure
they do not exceed the amperage limit of 1.0A for the PSSCENA.
•
Backplane current can be extended beyond 1.0A with a PSSSE24A Backplane Extension
Power Supply. Add multiple PSSSE24A modules to reach the 63 module maximum.
Cat. No.
PointBus Current Requirements
PSSN8xxx
75 mA
PSSP8xxx
75 mA
PSST8xxx
75 mA
PSSTR4M12A
90 mA
PSSNACM12A
75 mA
PSSNAVM12A
75 mA
PSSTACM12A
75 mA
PSSTAVM12A
75 mA
PSSS23A
75 mA
PSSV32A
75 mA
EtherNet/IP Communication Rate
10/100Mbits /s, half or full-duplex
Power Supply Specifications
Power Supply
Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a
NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV)
power supply to power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak
or 60VDC under normal conditions and under single fault conditions. A PELV supply has
the same rating and is connected to protected earth.
Input Voltage Rating
24VDC nominal
10-28.8VDC range
Inrush Current
6A maximum for 10ms
Field Side Power Requirements, Maximum
24VDC (+20% = 28.8VDC) @ 400 mA
Interruption
Output voltage will stay within specifications when input drops out for
10ms at 10V with maximum load
General Specifications
LED Indicators
1 green/red Adapter status
1 green Network activity
1 green/red Network status
1 green/red PointBus status
1 green System Power (PointBus 5V power)
1 green Adapter Power (24V from field supply)
Power Consumption, Maximum
8.1W @ 28.8VDC
Power Dissipation, Maximum
2.8W @ 28.8VDC
Thermal Dissipation, Maximum
9.5 BTU/hr. @ 28.8VDC
PointBus Output Current, Maximum
1A @ 5VDC ±5% (4.75 - 5.25)
Input Overvoltage Protection
Reverse polarity protected
Isolation Voltage
50V rms
(continuous-voltage withstand rating)
Tested to withstand 1250VAC rms for 60s
Field Power Bus
Nominal Voltage
24VDC
Supply Voltage
10-28.8VDC range
Supply Current
10A maximum
Dimensions
Inches (Millimeters) 4.41H x 2.83W x 2.56D (112H x 72W x 65D)
H Series Fieldbus EtherNet/IP Adapter, Series A (PSSCENA)
E104P
7
Specifications
Following are specifications for the PSSCENA EtherNet/IP adapter.
Summary of Contents for H Series
Page 135: ...DeviceNet Media Design and Installation Guide...
Page 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Page 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Page 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Page 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Page 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Page 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Page 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Page 263: ......
Page 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Page 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...