• Choose
Next to set RPI.
• Choose
Finish. Notice that the 1738-AENT is now under the
I/O configuration
H Series Fieldbus EtherNet/IP Adapter, Series A (PSSCENA)
E104P
5
Wire the EtherNet/IP Adapter
Following are wiring instructions for the EtherNet/IP Adapter.
Make sure all connectors and caps are securely tightened to
properly seal the connections against leaks and maintain IP67
requirements.
!
ATTENTION
Female In Connector
PSSCENA Network Connector (D-Coded M12)
(view into connector)
Pin 1 - Tx +
Pin 2 - Rx +
Pin 3 - Tx -
Pin 4 - Rx -
Male In Connector
PSSCENA Auxiliary Power (Mini 7/8")
(view into connector)
Pin 1 - User Power +
Pin 2 - Adapter Power +
Pin 3 - Adapter Power -
Pin 4 - User Power -
NOTE: User power is the 24VDC power for field devices.
Adapter power is the 24VDC power for adapter. It is converted to
5VDC to power H Series Fieldbus modules.
Summary of Contents for H Series
Page 135: ...DeviceNet Media Design and Installation Guide...
Page 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Page 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Page 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Page 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Page 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Page 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Page 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Page 263: ......
Page 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Page 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...