Publication DNET-UM072C-EN-P - July 2004
4-16
Determine Power Requirements
.
Two power supplies (end-connected) in parallel with no V+ break
The following example uses the look-up method to determine the
configuration for two end-connected power supplies. You must use diodes at
the power taps to prevent back-feeding of the power supplies. Check your
national and local codes for any restrictions on the use of parallel power
supplies. The NEC/CECode requires that the power supplies must be listed
for parallel operation.
IMPORTANT
To use this configuration, you must make the following
PowerTap tap modifications:
•
place no loads between the PowerTap taps
•
remove fuses between the two PowerTap taps to
segment the V+ conductor in the trunk line between
the taps
•
cut V+ (red) flush with cable jacket
remove
these
fuses
power
supply
power
supply
V+ V-
V- V+
CAN_H
CAN_L
drain
V+
V-
trunk line
ground
Wire
Color
Wire
identity
Use
white
CAN_H
signal
blue
CAN_L
signal
bare
drain
shield
black
V-
power
red
V+
power
41828
Summary of Contents for H Series
Page 135: ...DeviceNet Media Design and Installation Guide...
Page 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Page 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Page 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Page 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Page 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Page 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Page 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Page 263: ......
Page 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Page 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...