Publication DNET-UM072C-EN-P - July 2004
5-2
Correct and Prevent Network Problems
Use Rockwell Automation’s Media Checker (catalog number
1788-MCHKR; available from your local Rockwell Automation
distributor) to test network problems that result from miswiring,
loose connections, opens or shorts.
Be careful when setting network addresses and baud rates.
Incorrectly set addresses or baud rates will cause other nodes to
appear to be bad.
Pressing the reset button on the scanner does not reset the network
Cycling power to the rack does not reset the network
Cycling network power could cause the scanner to go bus off. In
this state, nodes will not re-allocate, even if they are functioning
correctly.
If, after you replace a node that has gone bus off, the problem
persists, the problem is not the node itself. Rather, the problem
could be the address or baud rate setting, or a network topology,
grounding, or noise problem.
Summary of Contents for H Series
Page 135: ...DeviceNet Media Design and Installation Guide...
Page 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Page 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Page 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Page 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Page 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Page 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Page 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Page 263: ......
Page 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Page 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...