H Series Fieldbus DeviceNet Adapters, Series A (PSSCDM12A, PSSCDM18PA)
E101P
6
Troubleshoot with the Indicators
DNet
Out
PSSCDM18PA
Adapter
Status
DeviceNet
Status
PointBus
Status
System
Power
Adapter
Power
DNet
In
X10
PWR
X1
PSSCDM18PA
Adapter Status
Indicator
DeviceNet Status
Indicator
PointBus Status
Indicator
System Power
Indicator
Adapter Power
Indicator
Indication
Probable Cause
Adapter Status
Off
No power applied to device
Green
Device operating normally
Flashing Red
Recoverable fault
Red
Unrecoverable fault -
may require device replacement
Flashing Red/Green Device is in self-test
Indication
Probable Cause
DeviceNet Status
Off
Device is not on line:
- Device attempting to Autobaud
- Device has not completed
dup_MAC-id test
- Device not powered - check module
status indicator
Flashing Green
Device is on line but has no
connections in the established state
Green
Device is on line and has
connections in the established state
Flashing Red
One or more I/O connections in
timed-out state
Red
Critical link failure - failed
communication device. Device
detected error that prevents it from
communicating on the network.
(Possible duplicate MAC ID or baud
rate mismatch).
Indication
Probable Cause
PointBus Status
Off
Device is not on line:
- Device has not completed
dup_MAC-id test
- Device not powered - check module
status indicator
Flashing Green
Device is on line but has no
connections in the established state
Green
Device is on line and has
connections in the established state
Flashing Red
One or more I/O connections in
timed-out state
Red
Critical link failure - failed
communication device. Device
detected error that prevents it from
communicating on the network.
(Possible duplicate MAC ID or baud
rate mismatch).
Flashing Red/Green Communication faulted device - the
device has detected a network access
error and is in communication faulted
state. Device has received and accepted
an Identity Communication Faulted
Request - long protocol message.
Indication
Probable Cause
System Power*
Off
Not active - Field power is off,
overloaded backplane or dc-dc
converter problem.
Green
System power on - dc-dc converter
active (5V).
Indication
Probable Cause
Adapter Power**
Off
Not active - Field power is off.
Green
System power on, 24V present.
* System Power Indicator shows the 5V power output from the dc-dc converter.
** Adapter Power Indicator shows the 24V power input to the dc-dc converter.
Summary of Contents for H Series
Page 135: ...DeviceNet Media Design and Installation Guide...
Page 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Page 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Page 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Page 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Page 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Page 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Page 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Page 263: ......
Page 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Page 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...