Publication PSS-UM001A-EN-P – December 2016
A-2
Specifi cations
General Specifi cations (continued)
Power Consumption, Maximum
8.1W @ 28.8VDC
Power Dissipation, Maximum
2.8W @ 28.8VDC
Thermal Dissipation, Maximum
9.5 BTU/hr. @ 28.8VDC
Isolation Voltage
50V rms
(continuous-voltage withstand rating)
Tested at 1250VAC rms for 60s
Field Power Bus
Nominal Voltage
24VDC
Supply Voltage
10-28.8VDC range
Supply Current
10A maximum
Dimensions
Inches (Millimeters) 4.41H x 2.83W x 2.56D (112H x 72W x 65D)
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
20 to 60°C (68 to 140°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5-95%
non-condensing
Shock
IEC60068-2-27 (Test Ea, Un-packaged Shock):
Operating
30g
Non-operating
50g
Vibration
IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
ESD Immunity
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B Immunity
IEC 61000-4-4:
±4kV at 5kHz on power ports
±3kV at 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
±2kV line-earth(CM) on shielded ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Emissions CSPR
11:
Group 1, Class A
Enclosure Type Rating
Meets IP65/66/67 (when marked)
Mounting Base Screw Torque
#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel
Wiring Category
1
1 - on power ports
1 - on communications ports
Weight
Imperial (Metric) 0.80 lb. (0.36 kg)
Certifi cations: (when product is marked)
c-UL-us UL Listed Industrial Control Equipment, certifi ed for US and Canada
CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
C-Tick
Australian Radio communications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
ODVA
ODVA conformance tested to DeviceNet specifi cations
1. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and
Grounding Guidelines”.
Summary of Contents for H Series
Page 135: ...DeviceNet Media Design and Installation Guide...
Page 144: ...Publication DNET UM072C EN P July 2004 Table of Contents iv...
Page 170: ...Publication DNET UM072C EN P July 2004 1 26 Get Started Notes...
Page 194: ...Publication DNET UM072C EN P July 2004 2 24 Identify Cable System Components Notes...
Page 212: ...Publication DNET UM072C EN P July 2004 3 18 Make Cable Connections Notes...
Page 238: ...Publication DNET UM072C EN P July 2004 4 26 Determine Power Requirements Notes...
Page 248: ...Publication DNET UM072C EN P July 2004 5 10 Correct and Prevent Network Problems Notes...
Page 250: ...Publication DNET UM072C EN P July 2004 A 2 Understand Select NEC Topics Notes...
Page 263: ......
Page 267: ...Isysnet Serial Bus System Selection Guide Pneumatic...
Page 287: ...H Series Fieldbus DeviceNet Adapters PSSCDM12A PSSCDM18PA User Manual...