Programming Your Application
1-55
690+ Series Frequency Inverter
MOTOR DATA
Designed for all Motor Control
Modes.
In this function block you enter the
details of the motor under control and
any available motor nameplate
information.
The Autotune feature will determine the
MAG CURRENT, STATOR RES,
LEAKAGE INDUC, MUTUAL INDUC
and ROTOR TIME CONST motor
model parameter.
The OVERLOAD parameter
determines the allowed level of motor
overload. This can be especially useful
when operating with motors smaller
than the inverter rating.
Note:
Do not attempt to control motors whose rated current is less than 25% of the
drive rated current. Poor motor control or Autotune problems may occur if you
do.
Motor Data
** VOLTS / HZ
–
[1157] CONTROL
MODE
–
** 5.50 kW
–
[1158] POWER
–
** 50.0 Hz
–
[1159] BASE
FREQUENCY
–
** 400.0 V
–
[1160] MOTOR
VOLTAGE
–
** 11.30 A
–
[ 64]
MOTOR CURRENT
–
** 3.39 A
–
[ 65]
MAG CURRENT
–
** 1445.0 rpm
–
[ 83]
NAMEPLATE RPM
–
** STAR
–
[124] MOTOR
CONNECTION
–
** 4 POLE
–
[ 84]
MOTOR POLES
–
** 0.90
–
[242] POWER
FACTOR
–
** 2.0
–
[1164] OVERLOAD
–
** 1.3625 Ohm
–
[119] STATOR
RES
–
** 43.37 mH
–
[120] LEAKAGE
INDUC
–
** 173.48 mH
–
[121] MUTUAL
INDUC
–
276.04 ms
–
[1163] ROTOR
TIME CONST
–
MMI Menu Map
1
SETUP
2
MOTOR CONTROL
3
MOTOR DATA
CONTROL
MODE
POWER
BASE
FREQUENCY
MOTOR
VOLTAGE
MOTOR
CURRENT
MAG
CURRENT
NAMEPLATE
RPM
MOTOR
CONNECTION
MOTOR
POLES
POWER
FACTOR
OVERLOAD
STATOR
RES
LEAKAGE
INDUC
MUTUAL
INDUC
ROTOR TIME CONST
Parameter Descriptions
CONTROL MODE
Range: Enumerated - see below
Determines the main method of motor control used by the inverter.
Enumerated Value : Control Mode
0 : VOLTS / HZ
1 : SENSORLESS VEC
2 : CLOSED-LOOP VEC
3 : 4-Q REGEN
POWER
Range
:
0.00 to 3000.00kW
This parameter contains the motor nameplate power.
BASE FREQUENCY
Range
:
7.5 to 1000.0Hz
This parameter contains the motor nameplate base frequency. Refer to FLUXING, page 1-38.
MOTOR VOLTAGE
Range:
0.0 to 575.0V
This parameter contains the motor nameplate voltage at base frequency. Refer to VOLTAGE
CONTROL, page 1-134.
MOTOR CURRENT
Range: 0.00 to 5000.00A
This parameter contains the motor nameplate full-load line current.
MAG CURRENT
Range
:
0.00 to 5000.00A
This parameter contains the motor model no-load line current as determined by the auto-tune.