Application Macros
5-23
690+ Series Frequency Inverter
Autotune
–
ACTIVE [604]
–
FALSE
FALSE
–
[603] ENABLE
–
Comms Control
–
COMMS SEQ [295]
–
FALSE
–
COMMS REF [270]
–
FALSE
–
COMMS STATUS[272]
–
0
–
COMMS COMMAND[273]
–
0
FALSE
–
[300] REMOTE COMMS SEL
–
TERMINALS/COMMS
–
[307] REMOTE SEQ MODES
–
TERMINALS/COMMS
–
[308] REMOTE REF MODES
–
0.0 s
–
[309] COMMS TIMEOUT
–
Local Control
REMOTE SEQ[297]
–
TRUE
REMOTE REF[257]
–
TRUE
LOCAL/REMOTE
–
[298] SEQ MODES
–
LOCAL/REMOTE
–
[265] REF MODES
–
REMOTE
–
[299] POWER UP MODE
–
FALSE
–
[281] SEQ DIRECTION
–
Pattern Gen
–
DRIVE FREQUENCY[591]
–
0.00 Hz
TRUE
–
[ 98] RANDOM PATTERN
–
3 kHz
–
[ 99] FREQ SELECT
–
** 2.0 s
–
[100] DEFLUX DELAY
–
Slew Rate Limit
TRUE – [ 60] ENABLE
–
500.0 Hz/s
–
[ 62] ACCEL LIMIT
–
500.0 Hz/s
–
[ 61] DECEL LIMIT
–
Slip Comp
FALSE
–
[ 82] ENABLE
–
** 150.0 rpm
–
[ 85] MOTORING LIMIT
–
** 150.0 rpm
–
[ 86] REGEN LIMIT
–
Dynamic Braking
–
BRAKING [ 81]
–
FALSE
TRUE
–
[ 80] ENABLE
–
100 Ohm
–
[ 77] BRAKE RESISTANCE
–
0.1 kW
–
[ 78] BRAKE POWER
–
25
–
[ 79] 1SEC OVER RATING
–
Motor Control
Stabilisation
TRUE – [128] ENABLE
–
Sequencing and Reference
Reference
SPEED DEMAND[255]
–
0.00 %
SPEED SETPOINT[254]
–
0.00 %
REVERSE [256]
–
FALSE
LOCAL SETPOINT[247]
–
0.00 %
LOCAL REVERSE[250]
–
FALSE
COMMS SETPOINT[770]
–
0.00 %
0.00 %
–
[245] REMOTE SETPOINT
–
0.00 %
–
[248] SPEED TRIM
–
110.00 %
–
[252] MAX SPEED CLAMP
–
-110.00 %
–
[253] MIN SPEED CLAMP
–
FALSE
–
[243] TRIM IN LOCAL
–
FALSE
–
[249] REMOTE REVERSE
–
Reference Jog
10.00 %
–
[246] SETPOINT
–
1.0 s
–
[261] ACCEL TIME
–
1.0 s
–
[262] DECEL TIME
–
Reference Ramp
–
RAMPING [698]
–
FALSE
LINEAR
–
[244] RAMP TYPE
–
** 10.0 s
–
[258] ACCEL TIME
–
** 10.0 s
–
[259] DECEL TIME
–
FALSE
–
[268] SYMMETRIC MODE
–
** 10.0 s
–
[267] SYMMETRIC TIME
–
10.00 /s^2
–
[692] SRAMP ACCEL
–
10.00 /s^2
–
[693] SRAMP DECEL
–
10.00 /s^3
–
[694] SRAMP JERK 1
–
10.00 /s^3
–
[695] SRAMP JERK 2
–
10.00 /s^3
–
[696] SRAMP JERK 3
–
10.00 /s^3
–
[697] SRAMP JERK 4
–
TRUE
–
[691] SRAMP CONTINUOUS
–
FALSE
–
[260] HOLD
–
Reference Stop
STOP RAMP
–
[279] RUN STOP MODE
–
10.0 s
–
[263] STOP TIME
–
0.10 %
–
[266] STOP ZERO SPEED
–
0.500 s
–
[284] STOP DELAY
–
RAMPED
–
[304] FAST STOP MODE
–
30.0 s
–
[275] FAST STOP LIMIT
–
0.1 s
–
[264] FAST STOP TIME
–
1200 Hz/s
–
[126] FINAL STOP RATE
–
Auto Restart
–
PENDING [608]
–
FALSE
–
RESTARTING [616]
–
FALSE
–
ATTEMPTS LEFT[614]
–
5
–
TIME LEFT [615]
–
0.0 s
FALSE
–
[611] ENABLE
–
5
–
[612] ATTEMPTS
–
10.0 s
–
[610] INITIAL DELAY 1
–
10.0 s
–
[613] ATTEMPT DELAY 1
–
0000
–
[609] TRIGGERS 1
–
0000
–
[744] TRIGGERS 1+
–
0.1 s
–
[678] INITIAL DELAY 2
–
0.1 s
–
[679] ATTEMPT DELAY 2
–
–
[677] TRIGGERS 2
–
–
[745] TRIGGERS 2+
–
0000
0000
0.00 %
Setpoint Scale
–
OUTPUT [ 59]
–
0.0 Hz
–
[ 58] INPUT
–
** 1500 RPM
–
[1032] MAX SPEED
–
Inverse Time
–
IT LIMITING [1152]
–
FALSE
–
INVERSE TIME OP [1153]
–
0.00 %
105.00 %
–
[1148] AIMING POINT
–
60.0 s
–
[1149] DELAY
–
10.0 s
–
[1150] DOWN TIME
–
120.0 s
–
[1151] UP TIME
–
Motor Data
** VOLTS / HZ
–
[1157]
CONTROL MODE
–
** 5.50 kW
–
[1158]
POWER
–
** 50.0 Hz
–
[1159]
BASE FREQUENCY
–
** 400.0 V
–
[1160]
MOTOR VOLTAGE
–
** 11.30 A
–
[ 64]
MOTOR CURRENT
–
** 3.39 A
–
[ 65]
MAG CURRENT
–
** 1445.0 rpm
–
[ 83]
NAMEPLATE RPM
–
** STAR
–
[124]
MOTOR CONNECTION
–
** 4
–
[ 84]
MOTOR POLES
–
** 0.90
–
[242]
POWER FACTOR
–
** 2.0
–
[1164]
OVERLOAD
–
** 1.3625 Ohm
–
[119]
STATOR RES
–
** 43.37 mH
–
[120]
LEAKAGE INDUC
–
** 173.48 mH
–
[121]
MUTUAL INDUC
–
276.04 ms
–
[1163]
ROTOR TIME CONST
–
Current Limit
150.00 %
–
[365] CURRENT LIMIT
–
TRUE
–
[686] REGEN LIM ENABLE
–
Flycatching
ACTIVE
[576]
–
FALSE
SETPOINT
[ 28]
–
0.00 %
FALSE
–
[570] ENABLE
–
ALWAYS
–
[571] START MODE
–
BIDIRECTIONAL
–
[572] SEARCH MODE
–
** 9.00 %
–
[573] SEARCH VOLTS
–
** 40.00 %
–
[ 32] SEARCH BOOST
–
** 10.0 s
–
[574] SEARCH TIME
–
5.0 Hz
–
[575] MIN SEARCH SPEED
–
** 3.0 s
–
[709] REFLUX TIME
–
Inj Braking
ACTIVE [583]
–
FALSE
** 0.5 s – [710] DEFLUX TIME
–
** 9.0 Hz
–
[577] FREQUENCY
–
100.00 %
–
[578] I-LIM LEVEL
–
** 2.0 s
–
[579] DC PULSE
–
** 1.0 s
–
[580] FINAL DC PULSE
–
** 4.00 %
–
[581] DC LEVEL
–
600.0 s
–
[582] TIMEOUT
–
** 100.00 %
–
[739] BASE VOLTS
–
Torque Limit
–
ACTUAL POS LIM [1212]
–
0.00 %
–
ACTUAL NEG LIM [1213]
–
0.00 %
150.00 %
–
[1208] POS TORQUE LIM
–
-150.00 %
–
[1209] NEG TORQUE LIM
–
150.00 %
–
[1210] MAIN TORQUE LIM
–
150.00 %
–
[1554] FAST STOP T-LIM
–
FALSE
–
[1211] SYMMETRIC LIM
–
Energy Meter
–
POWER [1604]
–
0.00 kW
–
POWER [1605]
–
0.00 HP
–
REACTIVE POWER [1606]
–
0.00 kVAr
–
ENERGY USED [1607]
–
0.0 kWh
FALSE
–
[1603] RESET
–
Feedbacks
–
DC LINK VOLTS [ 75]
–
0 V
–
TERMINAL VOLTS [1020]
–
0 V
–
SPEED FEEDBACK
RPM
[569]
–
0.00 rpm
–
SPEED FBK REV/S [568]
–
0.00 rev/s
–
SPEED FEEDBACK % [749]
–
0.00 %
–
ENCODER FBK % [1238]
–
0.00 %
–
ENCODER COUNT [1016]
–
0
–
TORQUE FEEDBACK [ 70]
–
0.00 %
–
FIELD FEEDBACK [ 73]
–
0.00 %
–
MOTOR CURRENT % [ 66]
–
0.00 %
–
MOTOR CURRENT [ 67]
–
0.0 A
** 10.0 V
–
[761] ENCODER SUPPLY
–
** 2048
–
[566] ENCODER LINES
–
**FALSE
–
[567] ENCODER INVERT
–
QUADRATURE
–
[565] ENCODER MODE
**FALSE
–
[ 50] QUADRATIC TORQUE
–
Fluxing
LINEAR LAW
–
[104] V/F SHAPE
–
* 50.0 Hz
–
[106] BASE FREQUENCY
–
** 0.00 %
–
[107] FIXED BOOST
–
** 0.00 %
–
[108] AUTO BOOST
–
0.00 %
–
[1656] ACCELRTN BOOST
–
FALSE
–
[1655] ENERGY SAVING
–
10.00 %
–
[1657] USER FREQ 1
–
10.00 %
–
[1658] USER VOLTAGE 1
–
20.00 %
–
[1659] USER FREQ 2
–
20.00 %
–
[1660] USER VOLTAGE 2
–
30.00 %
–
[1661] USER FREQ 3
–
30.00 %
–
[1662] USER VOLTAGE 3
–
40.00 %
–
[1663] USER FREQ 4
–
40.00 %
–
[1664] USER VOLTAGE 4
–
50.00 %
–
[1665] USER FREQ 5
–
50.00 %
–
[1666] USER VOLTAGE 5
–
60.00 %
–
[1667] USER FREQ 6
–
60.00 %
–
[1668] USER VOLTAGE 6
–
70.00 %
–
[1669] USER FREQ 7
–
70.00 %
–
[1670] USER VOLTAGE 7
–
80.00 %
–
[1671] USER FREQ 8
–
80.00 %
–
[1672] USER VOLTAGE 8
–
90.00 %
–
[1673] USER FREQ 9
–
90.00 %
–
[1674] USER VOLTAGE 9
–
100.00 %
–
[1675] USER FREQ 10
–
100.00 %
–
[1676] USER VOLTAGE 10
–
Power Loss Cntrl
–
PWR LOSS ACTIVE [1271]
–
FALSE
FALSE
–
[1265] ENABLE
–
** 447V
–
[1266] TRIP THRESHOLD
–
20V
–
[1267] CONTROL BAND
–
10.00s
–
[1268] ACCEL TIME
–
5.00s
–
[1269] DECEL TIME
–
0.00%
–
[1677] INITIAL STEP
–
30.00s
–
[1270] TIME LIMIT
–
Regen Control
–
SYNCHRONISING
[1641]
–
FALSE
–
SYNCHRONISED
[1642]
–
FALSE
–
PHASE LOSS
[1643]
–
FALSE
–
CLOSE PRECHARGE
[1644]
–
FALSE
–
ENABLE DRIVE
[1645]
–
FALSE
–
STATUS
[1646]
–
SUPPLY FREQ LOW
TRUE
–
[1633] PRECHARGE CLOSED
–
720V
–
[1634] DC VOLTS DEMAND
–
FALSE
–
[1678] BRAKE MODE
–
Sequencing Logic
–
TRIPPED
[289]
–
FALSE
–
RUNNING
[285]
–
FALSE
–
JOGGING
[302]
–
FALSE
–
STOPPING
[303]
–
FALSE
–
OUTPUT CONTACTOR [286]
–
FALSE
–
SWITCH ON ENABLE
[288]
–
FALSE
–
SWITCHED ON
[306]
–
FALSE
–
READY
[287]
–
FALSE
–
SYSTEM RESET
[305]
–
FALSE
–
SEQUENCER STATE
[301]
–
START DISABLED
–
REMOTE REV OUT
[296]
–
FALSE
–
HEALTHY
[274]
–
TRUE
–
FAN RUNNING [620]
–
FALSE
0.000s
–
[1686] START DELAY
–
FALSE
–
[291] RUN FORWARD
–
FALSE
–
[292] RUN REVERSE
–
FALSE
–
[293] NOT STOP
–
FALSE
–
[280] JOG
–
TRUE
–
[1235] CONTACTOR CLOSED
–
TRUE
–
[276] DRIVE ENABLE
–
TRUE
–
[277] NOT FAST STOP
–
TRUE
–
[278] NOT COAST STOP
–
FALSE
–
[294] REMOTE REVERSE
–
FALSE
–
[282] REM TRIP RESET
–
TRUE
–
[290] TRIP RST BY RUN
–
FALSE
–
[283] POWER UP START
–
Voltage Control
NONE
–
[595] VOLTAGE MODE
–
100.00 %
–
[112] BASE VOLTS
–
Speed Loop
–
TOTAL SPD DMD RPM
[1203]
–
0.00 RPM
–
TOTAL SPD DMD %
[1206]
–
0.00 %
–
SPEED ERROR
[1207]
–
0.00 %
–
TORQUE DEMAND
[1204]
–
0.00 %
–
DIRECT INPUT
[1205]
–
0.00 %
–
PHASE INPUT
[1397]
–
0.00 %
** 20.00
–
[1187] SPEED PROP GAIN
–
** 100 ms
–
[1188] SPEED INT TIME
–
FALSE
–
[1189] INT DEFEAT
–
0.00 %
–
[1190] SPEED INT PRESET
–
3.0 ms
–
[1191] SPEED DMD FILTER
–
1.5 ms
–
[1192] SPEED FBK FILTER
–
0.00 %
–
[1193] AUX TORQUE DMD
–
0.00 %
–
[1194] ADAPTIVE THRESH
–
0.00
–
[1195] ADAPTIVE P-GAIN
–
NONE
–
[1196] DIRECT IP SELECT
–
1.0000
–
[1197] DIRECT RATIO
–
110.00 %
–
[1198] DIRCT IP POS LIM
–
-110.00 %
–
[1199] DIRCT IP NEG LIM
–
110.00 %
–
[1200] SPEED POS LIM
–
-110.00 %
–
[1201] SPEED NEG LIM
–
FALSE
–
[1202] TORQ DMD ISOLATE
–
Macro Control Blocks
Some of these blocks may already be in use by the macros