Programming Your Application
1-129
690+ Series Frequency Inverter
Operation
Description
IF(C) HOLD A
If INPUT C is zero, the OUTPUT is set to INPUT A, otherwise the
OUTPUT is unchanged.
On powering up the drive, the output will be pre-loaded with the last saved
value of input B.
BINARY
DECODE
The OUTPUT is set according to which of the INPUTs are non-zero.
INPUT C
INPUT B INPUT A
OUTPUT
0
0
0 0.00
0 0
≠
0 1.00
0
≠
0
0
2.00
0
≠
0
≠
0
3.00
≠
0
0
0
4.00
≠
0 0
≠
0
5.00
≠
0
≠
0
0
6.00
≠
0
≠
0
≠
0
7.00
In the above table,
≠
0 indicates that the corresponding input is not zero.
ON DELAY
A programmable delay between receiving and outputting a Boolean TRUE
signal.
INPUT A becoming TRUE starts the delay timer. INPUT B sets the duration
of the delay in seconds (1 = 1 second). At the end of the duration, OUTPUT
becomes TRUE unless INPUT A has reverted to FALSE. Setting INPUT C
to TRUE (
≠
0) inverts the output.
OFF DELAY
A programmable delay between receiving and outputting a Boolean FALSE
signal.
INPUT A becoming FALSE starts the delay timer. INPUT B sets the
duration of the delay in seconds (1 = 1 second). Setting INPUT C to TRUE
(
≠
0) inverts the output. At the end of the duration, OUTPUT becomes
FALSE unless INPUT A has reverted to TRUE.
input A
output
input C FALSE
input C TRUE
Target time (input B)
t
input A
output
input C FALSE
input C TRUE
Target time (input B)
t