1-96
Programming Your Application
690+ Series Frequency Inverter
SEQUENCING LOGIC
This function block contains all the
parameters relating to the sequencing
(start and stop) of the Inverter.
Before the Inverter will respond to the
RUN FWD, RUN REV or JOG
parameters (cause the Inverter to run
or jog), the parameters DRIVE
ENABLE, NOT FAST STOP and
NOT COAST STOP need to be set to
TRUE. In addition, the Inverter needs
to be healthy (HEALTHY is TRUE).
The Inverter will only respond to
RUN FWD, RUN REV and JOG if
the Inverter is in the Remote
Sequencing mode.
If RUN FWD and RUN REV are
TRUE, both are ignored and the
Inverter will stop.
Sequencing Logic
–
TRIPPED [289]
–
FALSE
–
RUNNING [285]
–
FALSE
–
JOGGING [302]
–
FALSE
–
STOPPING [303]
–
FALSE
–
OUTPUT CONTACTOR [286]
–
FALSE
–
SWITCH ON ENABLE [288]
–
FALSE
–
SWITCHED ON [306]
–
FALSE
–
READY [287]
–
FALSE
–
SYSTEM RESET [305]
–
FALSE
–
SEQUENCER STATE [301]
–
START DISABLED
–
REMOTE REV OUT [296]
–
FALSE
–
HEALTHY [274]
–
TRUE
–
FAN RUNNING [620]
–
FALSE
0.000s
–
[1686] START DELAY
–
FALSE
–
[291] RUN FORWARD
–
FALSE
–
[292] RUN REVERSE
–
FALSE
–
[293] NOT STOP
–
FALSE
–
[280] JOG
–
TRUE
–
[1235] CONTACTOR CLOSED
–
TRUE
–
[276] DRIVE ENABLE
–
TRUE
–
[277] NOT FAST STOP
–
TRUE
–
[278] NOT COAST STOP
–
FALSE
–
[294] REMOTE REVERSE
–
FALSE
–
[282] REM TRIP RESET
–
TRUE
–
[290] TRIP RST BY RUN
–
FALSE
–
[283] POWER UP START
–
MMI Menu Map
1
SETUP
2
SEQ & REF
3
SEQUENCING LOGIC
START
DELAY
RUN
FORWARD
RUN
REVERSE
NOT
STOP
JOG
CONTACTOR
CLOSED
DRIVE
ENABLE
NOT FAST STOP
NOT COAST STOP
REMOTE
REVERSE
REM TRIP RESET
TRIP RST BY RUN
POWER UP START
TRIPPED
RUNNING
JOGGING
STOPPING
OUTPUT
CONTACTOR
SWITCH ON ENABLE
SWITCHED
ON
READY
SYSTEM
RESET
SEQUENCER
STATE
REMOTE REV OUT
HEALTHY
FAN
RUNNING
Parameter Descriptions
START DELAY
Range: 0.000 to 30.000s
Delays the action of "ramping to setpoint" from the Run command. This can allow a period for
motor flux to establish before the ramp to setpoint.
RUN FWD
Range: FALSE / TRUE
Setting this parameter to TRUE causes the Inverter to run in the forward direction.
RUN REV
Range: FALSE / TRUE
Setting this parameter to TRUE causes the Inverter to run in the reverse direction.
NOT STOP
Range: FALSE / TRUE
Setting this parameter TRUE will latch the RUN FWD or RUN REV commands. Once latched,
they can be reset to FALSE and the Inverter will continue to run. Setting NOT STOP to FALSE
causes the run commands to be unlatched.
JOG
Range: FALSE / TRUE
Setting this parameter TRUE causes the Inverter to run at the speed set by JOG SETPOINT
(refer to the REFERENCE JOG function block). Once jogging, setting JOG to FALSE causes
the Inverter to ramp to zero.
CONTACTOR CLOSED
Range: FALSE / TRUE
Feedback used to indicate that the external contactor has been closed. It must be TRUE for the
sequencer to proceed from the SWITCHED ON state to the READY STATE, refer to
SEQUENCER STATE.
DRIVE ENABLE
Range: FALSE / TRUE
This provides a means of electronically inhibiting Inverter operation. Whilst running, setting this
parameter to FALSE disables the Inverter operation and causes the motor to coast.
NOT FAST STOP
Range: FALSE / TRUE
Whilst running or jogging, setting this parameter to FALSE causes the Inverter to ramp to zero.
The rate is set by FAST STOP RATE in the STOP function block. The action of setting NOT
FAST STOP to TRUE is latched. The Inverter cannot be restarted until fast stop is completed.