![Parker 690+ series Product Manual Download Page 196](http://html.mh-extra.com/html/parker/690-series/690-series_product-manual_755642196.webp)
2-52
Parameter Specification
690+ Series Frequency Inverter
FRAME G - 400V Build Power Dependent Defaults
Constant Torque
Parameter
Function Block
Tag
110W
132kW
160kW
180kW
ACCEL TIME
REFERENCE RAMP
258
50.0
50.0
50.0
50.0
AUTO BOOST
FLUXING
108
0.00
0.00
0.00
0.00
BASE FREQUENCY
MOTOR DATA
1159
50.0
50.0
50.0
50.0
CONTROL MODE
MOTOR DATA
1157
VOLTS / HZ
VOLTS / HZ
VOLTS / HZ
VOLTS / HZ
DECEL TIME
REFERENCE RAMP
259
50.0
50.0
50.0
50.0
DEFLUX DELAY
PATTERN GEN
100
5.0
5.0
5.0
5.0
ENCODER INVERT
FEEDBACKS
567
FALSE
FALSE
FALSE
FALSE
ENCODER LINES
FEEDBACKS
566
2048
2048
2048
2048
ENCODER SUPPLY
FEEDBACKS
761
10.0
10.0
10.0
10.0
FIXED BOOST
FLUXING
107
0.00
0.00
0.00
0.00
INJ BASE VOLTS
INJ BRAKING
739
50.0
50.0
50.0
50.0
INJ DC LEVEL
INJ BRAKING
581
1.00
1.00
1.00
1.00
INJ DC PULSE
INJ BRAKING
579
3.0
3.0
3.0
3.0
INJ DEFLUX TIME
INJ BRAKING
710
2.0
2.0
2.0
2.0
INJ FINAL DC
INJ BRAKING
580
5.0
5.0
5.0
5.0
INJ FREQUENCY
INJ BRAKING
577
4.0
4.0
4.0
4.0
LEAKAGE INDUC
MOTOR DATA
120
2.66
2.27
2.00
1.66
MAG CURRENT
MOTOR DATA
65
55.20
64.80
73050
88.80
MAX SPEED
SETPOINT SCALE
1032
1500
1500
1500
1500
MOTOR CONNECTION
MOTOR DATA
124
STAR
STAR
STAR
STAR
MOTOR CURRENT
MOTOR DATA
64
184.00
216.00
245.00
296.00
MOTOR POLES
MOTOR DATA
84
4
4
4
4
MOTOR VOLTAGE
MOTOR DATA
1160
400.0
400.0
400.0
400.0
MOTOR VOLTS
VOLTAGE CONTROL
122
400.0
400.0
400.0
400.0
MOTORING LIMIT
SLIP COMP
85
150.0
150.0
150.0
150.0
MUTUAL INDUC
MOTOR DATA 121
10.65 9.08 8.00 6.62
NAMEPLATE RPM
MOTOR DATA
83
1480
1485
1485
1485
OVERLOAD MOTOR
DATA
1164
2.2
2.2
2.2
2.2
POWER MOTOR
DATA
1158
110.0
132.0
160.0
180.0
POWER FACTOR
MOTOR DATA
242
0.87
0.89
0.89
0.89
QUADRATIC TORQUE
FEEDBACKS
50 FALSE FALSE FALSE FALSE
REFLUX TIME
FLYCATCHING
709
6.0
6.0
6.0
6.0
REGEN LIMIT
SLIP COMP
86
150.0
150.0
150.0
150.0
ROTOR TIME CONST
MOTOR DATA
1163
759.12
1012.16
1012.16
1012.16
SEARCH BOOST
FLYCATCHING
32
10.0
10.0
10.0
10.0
SEARCH TIME
FLYCATCHING
574
15.0
15.0
15.0
15.0
SEARCH VOLTS
FLYCATCHING
573
8.0
8.0
8.0
8.0
SPEED INT TIME
SPEED LOOP
1188
100
100
100
100
SPEED PROP GAIN
SPEED LOOP
1187
20.00
20.00
20.00
20.00
STATOR RES
MOTOR DATA
119
0.0418
0.0356
0.0314
0.0260
SYMMETRIC TIME
REFERENCE RAMP
267
50.0
50.0
50.0
50.0
TRIP THRESHOLD
PWR LOSS CNTRL
1266
447
447
447
447
VHZ BASE FREQ
FLUXING
106
50.0
50.0
50.0
50.0