![Parker 690+ series Product Manual Download Page 159](http://html.mh-extra.com/html/parker/690-series/690-series_product-manual_755642159.webp)
Parameter Specification
2-15
690+ Series Frequency Inverter
TAG
MMI Name
Block
Type
Range
ID
Notes
64
MOTOR CURRENT
MOTOR DATA
REAL
0.00 to 999.99 A
1s
3,7,10
65
MAG CURRENT
MOTOR DATA
REAL
0.00 to 999.99 A
1t
3,10
66
MOTOR CURRENT %
FEEDBACKS
REAL
_.xx
1u
Output
67
MOTOR CURRENT A
FEEDBACKS
REAL
_.x
1v
Output
70 TORQUE
FEEDBACK FEEDBACKS REAL
_.xx
1y
Output
73 FIELD
FEEDBACK
FEEDBACKS REAL
_.xx
21
Output
74
PARAMETER
OPERATOR MENU 1
PREF
-1871 to 1871
22
75
DC LINK VOLTS
FEEDBACKS
REAL
_.
23
Output
77
BRAKE RESISTANCE
DYNAMIC BRAKING
REAL
1 to 1000 Ohm
25
7
78
BRAKE POWER
DYNAMIC BRAKING
REAL
0.1 to 510.0 kW
26
7
79
1SEC OVER RATING
DYNAMIC BRAKING
REAL
1 to 40
27
7
80
ENABLE
DYNAMIC BRAKING
BOOL
FALSE / TRUE
28
81 BRAKING
DYNAMIC
BRAKING
BOOL
FALSE / TRUE
29
Output
82
ENABLE
SLIP COMP
BOOL
FALSE / TRUE
2a
7
83
NAMEPLATE RPM
MOTOR DATA
REAL
0.0 to 30000.0 RPM
2b
3,10
84
MOTOR POLES
MOTOR DATA
ENUM
0 : 2 POLE
1 : 4 POLE
2 : 6 POLE
3 : 8 POLE
4 : 10 POLE
5 : 12 POLE
2c 3
85
MOTORING LIMIT
SLIP COMP
REAL
0.0 to 600.0 RPM
2d
3
86
REGEN LIMIT
SLIP COMP
REAL
0.0 to 600.0 RPM
2e
3
93
STARTUP SCREEN
ACCESS CONTROL
INT
0 to 16
2l
98
RANDOM PATTERN
PATTERN GEN
BOOL
FALSE / TRUE
2q
99
FREQ SELECT
PATTERN GEN
ENUM
0 : 3 kHz
1 : 6 kHz
2 : 9 kHz
2r 7
100
DEFLUX DELAY
PATTERN GEN
REAL
0.1 to 10.0 s
2s
3
101
HIGH LIMIT
DISPLAY SCALE 1
REAL
-32768.0000 to 32767.0000
2t
10
102
GROUP ID (GID)
SYSTEM PORT (P3)
INT
0 to 9
2u
103
UNIT ID (UID)
SYSTEM PORT (P3)
INT
0 to 15
2v
104
V/F SHAPE
FLUXING
ENUM
0 : LINEAR LAW
1 : FAN LAW
2 : USER DEFINED
2w
107
FIXED BOOST
FLUXING
REAL
0.00 to 25.00 %
2z
3
108
AUTO BOOST
FLUXING
REAL
0.00 to 25.00 %
30
3
115
OP DATABASE
OP STATION 1
BOOL
FALSE / TRUE
37
Output
117
MODE
SYSTEM PORT (P3)
ENUM
0 : EI ASCII
1 : 5703
39
119
STATOR RES
MOTOR DATA
REAL
0.0000 to 250.0000 Ohm
3b
3,10
120
LEAKAGE INDUC
MOTOR DATA
REAL
0.00 to 300.00 mH
3c
3
121
MUTUAL INDUC
MOTOR DATA
REAL
0.00 to 3000.00 mH
3d
3,10
124
MOTOR CONNECTION
MOTOR DATA
ENUM
0 : DELTA
1 : STAR
3g 3
125
FORMULA
DISPLAY SCALE 1
ENUM
0 : A/B * X + C
1 : A/B * (X+C)
2 : A/(B * X) + C
3 : A/(B * (X+C))
3h
126
FINAL STOP RATE
REFERENCE STOP
REAL
12 to 4800 Hz/s
3i
127
ENABLED KEYS
OP STATION 1
WORD
4 : DIRECTION
5 : JOG
6 : L/R
7 : START
3j
130
INPUT A
VALUE FUNC 1
REAL
-32768.00 to 32767.00
3m
131
INPUT B
VALUE FUNC 1
REAL
-32768.00 to 32767.00
3n
132
INPUT C
VALUE FUNC 1
REAL
-32768.00 to 32767.00
3o
133
OUTPUT
VALUE FUNC 1
REAL _.xx
3p