![Parker 690+ series Product Manual Download Page 22](http://html.mh-extra.com/html/parker/690-series/690-series_product-manual_755642022.webp)
1-14
Programming Your Application
690+ Series Frequency Inverter
Examples
Unipolar TYPE 0..+10V adjusted by the OFFSET parameter to give a bipolar reading.
Bipolar TYPE -10..+10V giving a bipolar reading.
Unipolar TYPE 0..20mA giving a unipolar reading.
+100%
10V (100%)
0%
5V (50%)
-100%
0V (0%)
VALUE
Parameter
200%
TYPE
Parameter
SCALE Parameter = 50% (200 x 0.5 = 100%)
OFFSET Parameter = 50% (10 x 0.5 = 5V)
TYPE Parameter = 0..+10V
100%
OFFSET
+100%
+10V (100%)
0%
0V (0%)
-100%
-10V (-100%)
VALUE
Parameter
200%
TYPE
Parameter
SCALE Parameter = 100% (no effect)
OFFSET Parameter = 0% (no effect)
TYPE Parameter = -10..+10V
200%
100%
20mA (100%)
50%
10mA (50%)
0%
0mA (0%)
VALUE
Parameter
100%
TYPE
Parameter
SCALE Parameter = 100% (no effect)
OFFSET Parameter = 0% (no effect)
TYPE Parameter = 0..+20mA
100%