![Parker 690+ series Product Manual Download Page 158](http://html.mh-extra.com/html/parker/690-series/690-series_product-manual_755642158.webp)
2-14
Parameter Specification
690+ Series Frequency Inverter
Specification Table: Tag Number Order
TAG
MMI Name
Block
Type
Range
ID
Notes
TAG MMI
NAME
Block
TYPE RANGE
ID NOTES
4
ACTIVE TRIPS
TRIPS STATUS
WORD
0000 to FFFF
4
Output
5
WARNINGS
TRIPS STATUS
WORD
0000 to FFFF
5
Output
6
FIRST TRIP
TRIPS STATUS
ENUM
Same as Tag 500
6
Output
8
PASSWORD
ACCESS CONTROL
WORD
0000 to FFFF
8
12
BREAK ENABLE
ANALOG INPUT 1
BOOL
FALSE / TRUE
0c
13
TYPE
ANALOG INPUT 1
ENUM
0 : 0..+10 V
1 : +2..+10 V
2 : 0..+5 V
3 : +1..+5 V
4 : -10..+10 V
5 : 0..20 mA
6 : 4..20 mA
7 : 20..4 mA
8 : 20..0 mA
9 : 0..+20 V
0d
14
SCALE
ANALOG INPUT 1
REAL
-300.00 to 300.00 %
0e
15
OFFSET
ANALOG INPUT 1
REAL
-300.00 to 300.00 %
0f
16
VALUE
ANALOG INPUT 1
REAL
_.xx
0g
Output
17
BREAK VALUE
ANALOG INPUT 1
REAL
-300.00 to 300.00 %
0h
18
BREAK
ANALOG INPUT 1
BOOL
FALSE / TRUE
0i
Output
21
BREAK ENABLE
ANALOG INPUT 2
BOOL
FALSE / TRUE
0l
22
TYPE
ANALOG INPUT 2
ENUM
Same as Tag 13
0m
23
SCALE
ANALOG INPUT 2
REAL
-300.00 to 300.00 %
0n
24
OFFSET
ANALOG INPUT 2
REAL
-300.00 to 300.00 %
0o
25
VALUE
ANALOG INPUT 2
REAL
_.xx
0p
Output
26
BREAK VALUE
ANALOG INPUT 2
REAL
-300.00 to 300.00 %
0q
27
BREAK
ANALOG INPUT 2
BOOL
FALSE / TRUE
0r
Output
28 SETPOINT
FLYCATCHING
REAL _.xx
0s
Output
30
INVERT
DIGITAL INPUT 1
BOOL
FALSE / TRUE
0u
31
VALUE
DIGITAL INPUT 1
BOOL
FALSE / TRUE
0v
Output
32 SEARCH
BOOST
FLYCATCHING
REAL
0.00 to 50.00 %
0w
3
33
INVERT
DIGITAL INPUT 2
BOOL
FALSE / TRUE
0x
34
VALUE
DIGITAL INPUT 2
BOOL
FALSE / TRUE
0y
Output
36
INVERT
DIGITAL INPUT 3
BOOL
FALSE / TRUE
10
37
VALUE
DIGITAL INPUT 3
BOOL
FALSE / TRUE
11
Output
39
INVERT
DIGITAL INPUT 4
BOOL
FALSE / TRUE
13
40
VALUE
DIGITAL INPUT 4
BOOL
FALSE / TRUE
14
Output
42
INVERT
DIGITAL INPUT 5
BOOL
FALSE / TRUE
16
43
VALUE
DIGITAL INPUT 5
BOOL
FALSE / TRUE
17
Output
44
COEFFICIENT B
DISPLAY SCALE 1
REAL
-32768.0000 to 32767.0000
18
10
45
VALUE
ANALOG OUTPUT 1
REAL
-300.00 to 300.00 %
19
46
SCALE
ANALOG OUTPUT 1
REAL
-300.00 to 300.00 %
1a
47
OFFSET
ANALOG OUTPUT 1
REAL
-300.00 to 300.00 %
1b
48
ABSOLUTE
ANALOG OUTPUT 1
BOOL
FALSE / TRUE
1c
49
TYPE
ANALOG OUTPUT 1
ENUM
0 : 0..+10 V
1 : 0..20 mA
2 : 4..20 mA
3 : -10..+10 V
4 : 20..4 mA
5 : 20..0 mA
6 : +2..+10 V
7 : 0..+5 V
8 : +1..+5 V
1d
50
QUADRATIC TORQUE
FEEDBACKS
BOOL
FALSE / TRUE
1e
3
51
INVERT
DIGITAL OUTPUT 1
BOOL
FALSE / TRUE
1f
52
VALUE
DIGITAL OUTPUT 1
BOOL
FALSE / TRUE
1g
53
LOW LIMIT
DISPLAY SCALE 1
REAL
-32768.0000 to 32767.0000
1h
10
54
INVERT
DIGITAL OUTPUT 2
BOOL
FALSE / TRUE
1i
55
VALUE
DIGITAL OUTPUT 2
BOOL
FALSE / TRUE
1j
58
INPUT
SETPOINT SCALE
REAL
-300.00 to 300.00 %
1m
59
OUTPUT
SETPOINT SCALE
REAL
_.x
1n
Output
60
ENABLE
SLEW RATE LIMIT
BOOL
FALSE / TRUE
1o
61
DECEL LIMIT
SLEW RATE LIMIT
REAL
1.0 to 1200.0 Hz/s
1p
62
ACCEL LIMIT
SLEW RATE LIMIT
REAL
1.0 to 1200.0 Hz/s
1q