Application Macros
5-16
690+ Series Frequency Inverter
Macro 6: “System” Drive
Provides for basic speed control with similar functionality to the 620 and 590+ Series Drives.
Control Wiring I/O
Terminal
Name
Purpose
Comment
2
ANALOG INPUT 1
Speed Setpoint
-10V = -100%, 10V = 100%
3
ANALOG INPUT 2
Speed Trim 1
-10V = -100%, 10V = 100%
4
ANALOG INPUT 3
Speed Trim 2
-10V = -100%, 10V = 100%
6
ANALOG OUTPUT 1
Ramp Output
absolute speed demand
0V = 0%, 10V = 100%
7
ANALOG OUTPUT 2
Speed
Feedback
-10V = -100%, 10V = 100%
8
ANALOG OUTPUT 3
Torque
Feedback
-10V = -100%, 10V = 100%
12
DIGITAL INPUT 1
Run Forward
24V = Run forward
13
DIGITAL INPUT 2
Run Reverse
24V = Run reverse
14
DIGITAL INPUT 3
Not Stop
24V = RUN FWD and RUN REV
signals latched
0V = RUN FWD and RUN REV
signals not latched
15
DIGITAL INPUT 4
Reverse
24V = Reverse
16
DIGITAL INPUT 5
Jog
24V = Jog
17
DIGITAL INPUT 6
Drive Enable
24V = Drive Enable
18
DIGITAL INPUT 7
Fast Stop
0V = Fast Stop
19
DIGITAL INPUT 8
Coast Stop
0V = Coast Stop
21, 22
DIGITAL OUTPUT 1
Health
0V = Tripped, i.e. not healthy
23, 24
DIGITAL OUTPUT 2
At Zero Speed
0V = At Zero Speed Feedback
25, 26
DIGITAL OUTPUT 3
Switched On
0V = Open,
24V = Swtiched On
The Operator Menu for Macro 6
The default Operator Menu is shown below.
SPEED DEMAND
DRIVE FREQUENCY
MOTOR CURRENT
TORQUE FEEDBACK
OPERATOR MENU
SETPOINT (REMOTE)
DC LINK VOLTS