Certification for the Converter
12-7
590 Series DC Digital Converter
Field Wiring Temperature Rating
Use 75
°
C copper conductors only.
Operating Ambient Temperature
For the operating ambient temperature range, refer to Chapter 11: “Technical Specifications”.
Field Wiring Terminal Markings
For the correct field wiring connections that are to be made to each terminal, refer to Chapter 3:
“Power Wiring Connections” and “Control Wiring Connections”.
Terminal Tightening Torque
Power and Control Field Wiring Terminals
For the correct tightening torque value, refer to Chapter 11: “Technical Specifications”.
Field Grounding Terminals
The field grounding terminal(s) is identified with the International Grounding Symbol
(IEC) Publication 417, Symbol 5019.
Field Terminal Kits
UL compliant Compression Lug Kits are available for the connection of power wiring for the
following Converter ratings. These lugs must be applied with the correct tooling as described in
the Installation Instructions provided with each Lug Kit.
Kit Part Number
Controller
Rating (A)
Number of
Lugs
Purpose
Wire Size
LA386000U035
35
5
AC/DC
8 AWG
(8.4 mm
2
)
LA386000U070
70
5
AC/DC
4 AWG
(21.2 mm
2
)
LA386000U110 110
3
2
AC
DC
2 AWG
(33.6 mm
2
)
1/0 AWG
(53.5 mm
2
)
LA386000U150 150
3
2
AC
DC
1/0 AWG
(53.5 mm
2
)
3/0 AWG
(85 mm
2
)
LA386000U180 180
3
2
AC
DC
3/0 AWG
(85 mm
2
)
4/0 AWG
(107.5 mm
2
)
LA386000U240
240
10 *
AC/DC
1/0 AWG
(53.5 mm
2
)
LA386000U270 270
6
*
4 *
AC
DC
1/0 AWG
(53.5 mm
2
)
2/0 AWG
(67.5 mm
2
)
LA386000U320 320
10*
AC/DC
3/0
AWG
(85mm
2
)
LA386000U450 450
6*
4*
AC
DC
250kcmil
(127mm
2
)
300 kcmil
(152mm
2
)
LA386000U720 720
10*
AC/DC
600kcmil
(304mm
2
)
* 2 cables and lugs are required per terminal.
Fuse Replacement Information
For fuse replacement information, refer to Chapter 11: “Technical Specifications”.
Summary of Contents for 590 series
Page 12: ...605 Frequency Inverter HA389591 Issue 1 Contents Contents Page Cont 12...
Page 16: ...1 4 Getting Started 590 Series Digital Converter...
Page 22: ...2 6...
Page 64: ...3 42 Installing the Converter 590D DC Digital Converter HA467078...
Page 82: ...4 18 Operating the Converter 590 Series DC Digital Converter...
Page 90: ...5 8 The Man Machine Interface MMI 590 Series DC Digital Converter...
Page 168: ...9 6 Control Loops 590 Series DC Digital Converter...
Page 222: ...13 14 Standard and Optional Equipment 590 Series DC Digital Converter...
Page 234: ...15 2 The Default Application 590 Series DC Digital Converter...
Page 242: ......