6-44
Programming Your Application
590 Series DC Digital Converter
RAMPS
This function block forms part of the
reference generation. It provides the facility
to control the rate at which the Converter
will respond to a changing setpoint.
MMI Menu Map
1
SETUP PARAMETERS
2
RAMPS
RAMP ACCEL TIME
RAMP DECEL TIME
RAMP HOLD
RAMP INPUT
% S-RAMP
RAMPING THRESH.
AUTO RESET
EXTERNAL RESET
RESET VALUE
MIN SPEED
RAMPS
RAMP OUTPUT [ 85]
–
0.00%
RAMPING [113]
–
FALSE
10.0 SECS
–
[ 2] RAMP ACCEL TIME
–
10.0 SECS
–
[ 3] RAMP DECEL TIME
–
OFF
–
[118] RAMP HOLD
–
0.00 %
–
[ 5] RAMP INPUT
–
2.50 %
–
[266] % S-RAMP
–
0.50 %
–
[286] RAMPING THRESH.
–
ENABLED
–
[287] AUTO RESET
–
DISABLED
–
[288] EXTERNAL RESET
–
0.00 %
–
[422] RESET VALUE
–
0.00 %
–
[126] MIN. SPEED
–
Parameter Descriptions
RAMP ACCEL TIME
Range: 0.1 to 600.0 SECS
Acceleration time (100% change)
RAMP DECEL TIME
Range: 0.1 to 600.0 SECS
Deceleration time (100% change)
RAMP HOLD
Range:
ON/OFF
While ON, the ramp output is held at its last value. This is overridden by
Ramp Reset
.
RAMP INPUT
Range: -100.00 to 100.00 %
Ramp Input TAG.
% S-RAMP
Range: 0.00 to 100.00 %
Percentage of ramp with S-shaped rate of change. A value of zero is equivalent to a linear
ramp. Changing this value affects the ramp times.
RAMPING THRESH.
Range: 0.00 to 100.00 %
Ramping flag threshold level. The threshold is used to detect whether the ramp is active.
AUTO RESET
Range:
ENABLED/DISABLED
If TRUE, then the ramp is reset whenever SYSTEM RESET is TRUE, that is each time the
Speed/Current loop is unquenched. (SYSTEM RESET Tag No. 374 is an internal flag that is
set TRUE for one cycle after the Speed/Current loop is enabled, i.e. every time the drive is
started).
EXTERNAL RESET
Range:
ENABLED/DISABLED
If TRUE, then the ramp is held in reset. EXTERNAL RESET does not depend on AUTO
RESET for its operation.
RESET VALUE
Range: -300.00 to 300.00 %
This value is pre-loaded into the output when RAMP RESET is TRUE, or at power-up. In
order to catch a spinning load smoothly (`bumpless transfer’) connect SPEED FEEDBACK
Tag No. 62 (source) to RESET VALUE Tag No. 422 (destination).
Summary of Contents for 590 series
Page 12: ...605 Frequency Inverter HA389591 Issue 1 Contents Contents Page Cont 12...
Page 16: ...1 4 Getting Started 590 Series Digital Converter...
Page 22: ...2 6...
Page 64: ...3 42 Installing the Converter 590D DC Digital Converter HA467078...
Page 82: ...4 18 Operating the Converter 590 Series DC Digital Converter...
Page 90: ...5 8 The Man Machine Interface MMI 590 Series DC Digital Converter...
Page 168: ...9 6 Control Loops 590 Series DC Digital Converter...
Page 222: ...13 14 Standard and Optional Equipment 590 Series DC Digital Converter...
Page 234: ...15 2 The Default Application 590 Series DC Digital Converter...
Page 242: ......