Programming Your Application
6-55
590 Series DC Digital Converter
ADVANCED
This function block is viewed in three
menus on the MMI and contains the
parameters for the advanced-user.
The ADVANCED MMI menu only
contains the I GAIN IN RAMP parameter.
ADAPTION
This MMI menu contains parameters for
speed loop gain scheduling.
ZERO SPD. QUENCH
Similar to Standstill logic (i.e. it stops
making current but keeps the contactor in) except that the speed loop remains enabled and will
cause the current loop to unquench very quickly.
MMI Menu Map
1
SETUP PARAMETERS
2
SPEED LOOP
3
ADVANCED
4
ADAPTION
MODE
SPD BRK 1 (LOW)
SPD BRK 2 (HIGH)
PROP.
GAIN
INT. TIME CONST.
MMI Menu Map
1
SETUP PARAMETERS
2
SPEED LOOP
3
ADVANCED
I GAIN IN RAMP
POS. LOOP P GAIN
ADVANCED
0
–
[268] MODE
–
1.00 %
–
[269] SPD BRK 1 (LOW)
–
5.00 %
–
[270] SPD BRK 2 (HIGH)
–
5.00
–
[271] PROP. GAIN
–
0.500 SECS
–
[272] INT. TIME CONST.
–
1.0000
–
[274] I GAIN IN RAMP
–
0.00%
–
[273] POS. LOOP P GAIN
–
0.50 %
–
[284] ZERO SPD. LEVEL
–
1.50 %
–
[285] ZERO IAD LEVEL
–
MMI Menu Map
1
SETUP PARAMETERS
2
SPEED LOOP
3
ZERO SPD. QUENCH
ZERO SPD. LEVEL
ZERO IAD LEVEL
Parameter Descriptions
MODE
Range: 0 to 3
0 - Disabled
1 - Speed Feedback Dependent
2 - Speed Error Dependent
3 - Current Demand Dependent
SPD BRK 1 (LOW)
Range: 0.00 to 100.00 %
IF
MODE
= 1
Then
BRK-points
correspond to speed feedback.
ELSE IF
MODE
= 2
Then
BRK-points
correspond to speed error.
ELSE IF
MODE
= 3
Then
BRK
-points correspond to current demand.
SPD BRK 2 (HIGH)
Range: 0.00 to 100.00 %
Above SPD BRK 2 (HIGH) the normal gains (as per main menu above) prevail.
Between the two break-points, a linear variation of the gains is implemented.
PROP. GAIN
Range: 0.00 to 200.00
Prop gain used below SPD BRK 1 (LOW)
INT. TIME CONST.
Range: 0.001 to 30.000 SECS
Integral time constant used below SPD BRK 1 (LOW)
I GAIN IN RAMP
Range: 0.0000 to 2.0000
While the RAMPING (Tag No. 113) flag is TRUE the integral gain is scaled by I GAIN IN
RAMP. This can be used to help prevent integral wind-up while the drive is ramping
(particularly high inertia loads).
POS. LOOP P GAIN
Reserved parameter for use by Parker SSD Drives.
ZERO SPD. LEVEL
Reserved parameter for use by Parker SSD Drives.
ZERO IAD LEVEL
Reserved parameter for use by Parker SSD Drives.
Summary of Contents for 590 series
Page 12: ...605 Frequency Inverter HA389591 Issue 1 Contents Contents Page Cont 12...
Page 16: ...1 4 Getting Started 590 Series Digital Converter...
Page 22: ...2 6...
Page 64: ...3 42 Installing the Converter 590D DC Digital Converter HA467078...
Page 82: ...4 18 Operating the Converter 590 Series DC Digital Converter...
Page 90: ...5 8 The Man Machine Interface MMI 590 Series DC Digital Converter...
Page 168: ...9 6 Control Loops 590 Series DC Digital Converter...
Page 222: ...13 14 Standard and Optional Equipment 590 Series DC Digital Converter...
Page 234: ...15 2 The Default Application 590 Series DC Digital Converter...
Page 242: ......