Programming Your Application
6-21
590 Series DC Digital Converter
DIGITAL INPUT (C5)
Tag No. 70 - D:34
ON/OFF
Electronic enable/quench terminal (ON = Enabled).
(Refer to DIGITAL INPUTS, page 6-24 and AUX I/O, page 6-8)
DIGIN 1 (C6)
Tag No. 71 - D:35
ON/OFF
Symmetrical current clamps/Asymmetrical (bipolar) current clamps (ON = Bipolar).
(Refer to DIGITAL INPUTS, page 6-24)
DIGIN 2 (C7)
Tag No. 72 - D:36
ON/OFF
Ramp hold input (ON = Hold).
(Refer to DIGITAL INPUTS, page 6-24)
DIGIN 3 (C8)
Tag No. 73 - D:37
ON/OFF
Current demand isolate; giving speed or current mode of operation. (ON = Current mode).
(Refer to DIGITAL INPUTS, page 6-24)
DIGOUT 1 (B5)
Tag No. 74 - D:38
ON/OFF
At zero speed.
(Refer to DIGITAL OUTPUTS, page 6-26)
DIGOUT 2 (B6)
Tag No. 75 - D:39
ON/OFF
Drive healthy. Health is also displayed on the front panel LED, always ON when the start is
low.
(Refer to DIGITAL OUTPUTS, page 6-26)
DIGOUT 3 (B7)
Tag No. 76 - D:40
ON/OFF
Drive ready to run (all alarms healthy and mains synchronisation achieved)
(Refer to DIGITAL OUTPUTS, page 6-26)
RAISE/LOWER O/P
Tag No. 264 - D:41
-300.00% to 300.00%
(OUTPUT) Value of the raise/lower ramp function.
(Refer to RAISE/LOWER, page 6-42
)
PID OUTPUT
Tag No. 417 - D:42
-315.00% to 315.00%
PID block output.
(Refer to PID, page 6-39)
PID CLAMPED
Tag No. 416 - D:43
TRUE/FALSE
Logic output indicating whether the PID limits are active.
(Refer to PID, page 6-39)
PID ERROR
Tag No. 415 - D:44
-105.00% to 105.00%
PID error = Input 1 - Input 2
(Refer to PID, page 6-39)
SPT SUM 1 OUTPUT
Tag No. 86 - D:45
-200.00% to 200.00%
Setpoint sum 1 output.
(Refer to SETPOINT SUM 1, page 6-48)
RAMP OUTPUT
Tag No. 85 - D:46
-100.00% to 100.00%
Setpoint ramp output.
(Refer to RAMPS, page 6-44)
SPEED SETPOINT
Tag No. 63 - D:47
-300.00% to 300.00%
Speed loop total setpoint including the ramp output before the ramp-to-zero function.
(Refer to SPEED LOOP, page 6-51)
TERMINAL VOLTS
Tag No. 57 - D:48
-125.00% to 125.00%
Scaled terminal volts.
(Refer to
CALIBRATION, page 6-11)
BACK EMF
Tag No. 60 - D:49
-150.00% to 150.00%
Calculated motor back EMF including IR. compensation.
(Refer to
CALIBRATION, page 6-11)
TACH INPUT (B2)
Tag No. 308 - D:50
-300.00% to 300.00%
Scaled analog tachogenerator feedback.
(Refer to
CALIBRATION, page 6-11)
ENCODER
Tag No. 206 - D:51
0 RPM to 6000 RPM
Encoder speed feedback in RPM.
(Refer to
CALIBRATION, page 6-11)
Summary of Contents for 590 series
Page 12: ...605 Frequency Inverter HA389591 Issue 1 Contents Contents Page Cont 12...
Page 16: ...1 4 Getting Started 590 Series Digital Converter...
Page 22: ...2 6...
Page 64: ...3 42 Installing the Converter 590D DC Digital Converter HA467078...
Page 82: ...4 18 Operating the Converter 590 Series DC Digital Converter...
Page 90: ...5 8 The Man Machine Interface MMI 590 Series DC Digital Converter...
Page 168: ...9 6 Control Loops 590 Series DC Digital Converter...
Page 222: ...13 14 Standard and Optional Equipment 590 Series DC Digital Converter...
Page 234: ...15 2 The Default Application 590 Series DC Digital Converter...
Page 242: ......