Serial Communications
14-3
590 Series DC Digital Converter
UDP Menu Structure
......SYSTEM PORT (P3)
........P3 SETUP
..........MODE //
Disable/5703 Setup Mode
..........5703 SUPPORT //
Submenu for 5703 parameters
..........P3 BAUD RATE //
Baud rate for the P3 Port
........DUMP MMI -> P3 //
Transfer the MMI to Host
........UDP XFER <- P3 //
Transfer Parameters From Host
........UDP XFER -> P3 //
Transfer Parameters To Host
SYSTEM PORT (P3) Setup
Set MODE parameter (Tag No. 130) to DISABLE (default) using the
MMI
Set P3 BAUD RATE parameter (Tag No. 198) to 9600 (default) using
the MMI
1 Stop bit (fixed)
NO Parity (fixed)
8 bits (fixed)
XON/XOFF Handshaking (fixed)
UDP Transfer Procedure
UDP UpLoad (UDP XFER <- P3)
This is the transfer of the parameters from the host computer to the Converter. This information
is written directly to EEprom, so
all the drive's current settings will
be overwritten
.
•
Connect the Converter to the host using the appropriate lead.
•
Using a standard communications package prepare the host to
transfer an ASCII file. Remember to set up the host's serial port first.
•
Set the P3 MODE parameter to DISABLE.
•
Start uploading on the Converter by selecting UDP XFER <- P3 on the MMI and pressing
the UP (
↑
) key, as instructed.
•
When the Converter says RECEIVING, begin the file transmission.
•
The file ends in a
:00000001FF
which the Converter uses to close the file.
•
As indicated, reset the Converter by pressing the
E
key.
UDP Download (UDP XFER -> P3)
This is the transfer of the parameters from the Converter to a host computer. This information
fully describes the Converter's settings in a Binary format.
•
Connect the Converter to the host using the appropriate lead.
•
Using a standard communications package prepare the host to receive an ASCII file.
Remember to set up the host's serial port first.
•
Perform a PARAMETER SAVE of the Converter's settings. This ensures the Dump matches
the Converter’s settings, (the listing is of the Converter's currently saved settings, i.e. held in
EEprom.
•
Set the P3 MODE parameter to DISABLE.
•
Prepare the host PC to receive a file; use the file extension .UDP to differentiate it from
.MMI format files.
•
Start downloading on the Converter by selecting UDP XFER -> P3 on the MMI and pressing
the UP (
↑
) key, as instructed.
MMI Menu Map
1
SERIAL LINKS
2
SYSTEM PORT P3
3
P3 SETUP
MODE
P3 BAUD RATE
MMI Menu Map
1
SERIAL LINKS
2
SYSTEM PORT P3
DUMP MMI -> P3
UDP XFER <- P3
UDP XFER -> P3
Summary of Contents for 590 series
Page 12: ...605 Frequency Inverter HA389591 Issue 1 Contents Contents Page Cont 12...
Page 16: ...1 4 Getting Started 590 Series Digital Converter...
Page 22: ...2 6...
Page 64: ...3 42 Installing the Converter 590D DC Digital Converter HA467078...
Page 82: ...4 18 Operating the Converter 590 Series DC Digital Converter...
Page 90: ...5 8 The Man Machine Interface MMI 590 Series DC Digital Converter...
Page 168: ...9 6 Control Loops 590 Series DC Digital Converter...
Page 222: ...13 14 Standard and Optional Equipment 590 Series DC Digital Converter...
Page 234: ...15 2 The Default Application 590 Series DC Digital Converter...
Page 242: ......