6-30
Programming Your Application
590 Series DC Digital Converter
INHIBIT ALARMS
This function block provides a view into
the current and past trip conditions, and
allows some trips to be disabled.
ALARMS
–
READY [125]
–
NOT READY
–
HEALTHY [122]
–
HEALTHY
–
HEALTH WORD [115]
–
0x0210
–
HEALTH STORE [116]
–
OK
ENABLED
–
[ 19] FIELD FAIL
–
ENABLED
–
[111] 5703 RCV ERROR
–
DISABLED
–
[ 28] STALL TRIP
–
TRUE
–
[305] TRIP RESET
–
ENABLED
–
[ 81] SPEED FBK ALARM
–
ENABLED
–
[ 92] ENCODER ALARM
–
MMI Menu Map
1
SETUP PARAMETERS
2
INHIBIT ALARMS
FIELD
FAIL
5703 RCV ERROR
STALL
TRIP
TRIP
RESET
SPEED FBK ALARM
ENCODER
ALARM
Parameter Descriptions
FIELD FAIL
Range:
ENABLED/INHIBITED
Inhibits the field fail alarm.
5703 RCV ERROR
Range:
ENABLED/INHIBITED
Inhibits 5703 serial communications receive error. Only active in Slave Mode.
STALL TRIP
Range:
ENABLED/INHIBITED
Inhibits the stall trip alarm from tripping the contactor out.
TRIP RESET
Range:
TRUE/FALSE
When this is FALSE the faults are latched permanently and the HEALTHY output remains
inactive after toggling the Start input (C3) off/on. The Trip Reset must then be set to TRUE for
the faults to be reset and the HEALTHY output to go active (high) when C3 goes low. This
feature can be used in applications where you want to reset the faults under your own control,
rather than automatically with the Start/Run command.
SPEED FBK ALARM
Range:
ENABLED/INHIBITED
Inhibits the speed feedback alarm.
ENCODER ALARM
Range:
ENABLED/INHIBITED
Inhibits the encoder option board alarm.
READY
Reserved parameter for use by Parker SSD Drives.
HEALTHY
Reserved parameter for use by Parker SSD Drives.
HEALTH WORD
Range: 0000 to FFFF
The hexadecimal sum of any alarms present. Refer to Chapter 7: “Trips and Fault Finding” -
Alarm Messages.
HEALTH STORE
Range: 0000 to FFFF
The hexadecimal value of the first (or only) alarm. Refer to Chapter 7: “Trips and Fault Finding”
- Alarm Messages.
Summary of Contents for 590 series
Page 12: ...605 Frequency Inverter HA389591 Issue 1 Contents Contents Page Cont 12...
Page 16: ...1 4 Getting Started 590 Series Digital Converter...
Page 22: ...2 6...
Page 64: ...3 42 Installing the Converter 590D DC Digital Converter HA467078...
Page 82: ...4 18 Operating the Converter 590 Series DC Digital Converter...
Page 90: ...5 8 The Man Machine Interface MMI 590 Series DC Digital Converter...
Page 168: ...9 6 Control Loops 590 Series DC Digital Converter...
Page 222: ...13 14 Standard and Optional Equipment 590 Series DC Digital Converter...
Page 234: ...15 2 The Default Application 590 Series DC Digital Converter...
Page 242: ......