9-40
Function Parameters
AC10 Inverter
ensuring that the motor is disconnected from the load. Set F801-805 and F810 correctly prior to
running testing.
Operation process of rotating tuning: Press the “I” key on the keypad to display “TEST”, and it
will tune the motor’s parameter in two stages. After that, the motor will accelerate according to
acceleration time set at F114 and maintain it for a certain period. The motor will then decelerate
to 0 according to the time set at F115. After auto-checking is completed, relevant parameters of
the motor will be stored in function codes F806~F809, and F800 will turn to 0 automatically.
F800
=
2
, stationary tuning.
It is useful in some cases where it is impossible to disconnect the motor from the load.
Press the “I” key, and the inverter will display “TEST”, and it will tune the motor‘s parameter in
two stages. The motor’s stator resistance, rotor resistance and leakage inductance will be
stored in F806-F809 automatically (the motor’s mutual inductance uses default value generated
according to the power), and F800 will turn to 0 automatically. The user may also calculate and
input the motor’s mutual inductance value manually according to actual conditions of the motor.
With regard to calculation formula and method, contact Parker for consultation.
When tuning the motor’s parameter, motor is not running but it is powered on. Do not touch
motor during this process.
*Note:
1.
No matter which tuning method of the motor parameters is adopted, set the information of the
motor (F801-F805) correctly according to the nameplate of the motor. If the operator is quite
familiar with the motor, the operator may input all the parameters (F806-F809) of the motor
manually.
2
. Parameter F804 can only be checked, not modified.
3.
Incorrect motor parameters may result in unstable running of the motor or even failure of
normal running. Correct tuning of the parameters is a requirement of vector control
performance.
Each time when F801 rated power of the motor is changed, the parameters of the motor
(F806-F809) will be refreshed to default settings automatically. Therefore, be careful while
amending this parameter.
The motor’s parameters may change when the motor heats up after running for a long time. If
the load can be disconnected, we recommend auto-checking before each running.
F810 is motor rated frequency.
When F104=3, and F810=60.00, F802 will change to 460V automatically, F805 will change to
1800 automatically.
When F104=3, and F810=50.00, F802 will change to 380V automatically, F805 will change to
1460 automatically.
When F810 is set to the other values, F802 and F805 will not change automatically.
F802 and F805 can be set manually.
F806 Stator resistance
Setting range:
0.001
~
65.53Ω (for 22kw and below 22kw)
0.1~6553mΩ (for above 22kw)
Subject to inverter
model
F807 Rotor resistance
Setting range:
0.001
~
65.53Ω (for 22kw and below 22kw)
0.1~6553mΩ (for above 22kw)
Subject to inverter
model
F808 Leakage inductance
Setting range:
0.01
~
655.3mH (for 22kw and below 22kw)
0.001~65.53mH (for above 22kw)
Subject to inverter
model
F809 Mutual inductance
Setting range:
0.01
~
655.3mH (for 22kw and below 22kw)
0.001~65.53mH (for above 22kw)
Subject to inverter
model
The set values of F806
~
F809 will be updated automatically after normal completion of
parameter tuning of the motor.