Function Parameters
9-3
AC10 Inverter
F114 First Acceleration Time (S)
Setting range:
0.1
~
3000
Mfr’s value:
subject to inverter
model
F115 First Deceleration Time (S)
F116 Second Acceleration Time (S)
F117 Second Deceleration Time (S)
F119 is used to set the reference of setting accel/decel time.
The Acceleration/Deceleration time can be chosen by multifunction digital input terminals
F316~F323 and connecting DI terminal with CM terminal. Please refer to the instructions of
multi-functional input terminals.
Note: When Flycatching is working, acceleration/deceleration time, min frequency and target
frequency are invalid. After Flycatching is finished, inverter will run to target frequency according to
acceleration/deceleration time.
F118 Base Frequency (Hz)
Setting range:
15.00
~
590.0
Mfr’s value:
50.00Hz
Base frequency is the final frequency of VVVF curve, and also is the least frequency according
to the highest output voltage.
When running frequency is lower than this value, inverter has constant-torque output. When
running frequency exceeds this value, inverter has constant-power output.
Note: During the process of Flycatching, base frequency is invalid. After Flycatching is
finished, this function code if valid.
F119 The reference of setting
accel/decel time
Setting range:
0: 0~50.00Hz
1: 0~F111
Mfr’s value: 0
When F119=0, acceleration/ deceleration time means the time for inverter to accelerate/
decelerate from 0Hz (50Hz) to 50Hz (0Hz).
When F119=1, acceleration/ deceleration time means the time for inverter to accelerate/
decelerate from 0Hz (max frequency) to max frequency (0Hz).
F120 Forward / Reverse Switchover
dead-Time (S)
Setting range:
0.0
~
3000
Mfr’s value: 0.0
Within “forward/ reverse switchover dead-time”, this latency time will be cancelled and the
inverter will switch to run in the other direction immediately upon receiving “stop” signal. This
function is suitable for all the speed control modes except automatic cycle operation.
This function can ease the current impact in the process of direction switchover.
Note: During the process of Flycatching. F120 is invalid. After Flycatching is finished, this
function code is valid.
F122 Reverse Running Forbidden
Setting range:
0: invalid;
1: valid
Mfr’s value: 0
When F122=1, inverter will only run forward no matter the state of terminals and the parameters set
by F202.
Inverter will not run reverse and forward / reverse switchover is forbidden. If reverse signal is given,
inverter will stop.
If reverse running locking is valid (F202=1), inverter has no output.
When F122=1
,
F613=1
,
F614≥2 and inverter gets forward running command and motor is rotating
www.comoso.com