Grounding – The pressure wire connector intended for connection for field installed equipment,
grounding conductor shall be plainly identified such as being marked “G”, “GRD”, “Ground”,
“Grounding”, or equivalent or with the grounding symbol (IEC 417, Symbol 5019).
Tightening torque and wire range for field grounding wiring terminals are marked adjacent to
the terminal or on the wiring diagram.
Frame Size
Terminal Type
Required Torque (in-lbs)
Wire Range (AWG)
10G-31-0015-XX
10G-31-0025-XX
10G-31-0035-XX
10G-31-0045-XX
10G-32-0050-XX
10G-32-0070-XX
10G-32-0100-XX
10G-11-0015-XX
10G-11-0025-XX
10G-11-0035-XX
10G-11-0045-XX
10G-12-0050-XX
10G-12-0070-XX
10G-12-0010-XX
10G-41-0006-XX
10G-41-0010-XX
10G-41-0015-XX
10G-42-0020-XX
10G-42-0030-XX
10G-42-0040-XX
10G-42-0065-XX
10G-43-0080-XX
10G-43-0090-XX
10G-43-0120-XX
10G-44-0170-XX
10G-44-0230-XX
10G-45-0320-XX
10G-45-0380-XX
10G-45-0440-XX
Grounding
Terminal Block
6.2
8
10G-46-0600-XX
39.0
6
10G-47-0750-XX
96.0
6
10G-47-0900-XX
96.0
6
10G-48-1100-XX
96.0
6
10G-48-1500-XX
96.0
4
10G-49-1800-XX
189.0
3
10G-49-2200-XX
189.0
3
10G-410-2650-XX
96.0
2
10G-411-3200-XX
96.0
1
10G-411-3600-XX
96.0
1