The Default Applications
13-11
AC10 Inverter
A simple application using a Proportional-Integral-Derivative 3-term controller. The set-point is
taken from AI1, with feedback signal from the process on AI2. The difference between these
two signals is taken as the PID error. The output of the PID block is then used as the drive
set-point.
Function setting
Setting value
F228 Macro selecting
5: PID control
F106 Control mode
2: VF control
F203 Main frequency source X
9: PID control
F316 DI1 terminal function setting
1: Running terminal
F317 DI2 terminal function setting
58: forward running
F318 DI3 terminal function setting
52: direction
F319 DI4 terminal function setting
2: stop
F320 DI5 terminal function setting
8: free stop
F431 AO1 analog output signal selecting
0: running frequency
FA01 PID adjusting target given source
1: AI1
FA02 PID adjusting feedback given source
2: AI2
1
2
3
5
6
4
7
8
9
10
11
12
13
14
15
16
17
18
TA
TB
TC
1
DO
24
V
CM
DI1
DI2
DI3
DI4
DI5
10
V
1
AI
2
AI
GND
1
AO
A
+
B
-
REF
Stop
Jog
Direction
Run
Feedback
source
not used
not used
Analog output F 431=0 , running
frequency is output .
GND
Feedback source AI 2 input 4-20 mA
Speed setpoint AI1 input 0-10V
10V
Coast stop
Stop
Jog
The jogging direction is
controlled by DI2.
Direction
inverter runs reverse .
Run
CM
24V
not used
Relay output
Given source