9-34
Function Parameters
AC10 Inverter
This parameter is used for starting and stopping a motor with high inertia. A motor with high
inertia will take a long time to stop completely. By setting this parameter, the user does not need
to wait for the motor to come to a complete stop before restarting the AC motor drive.
F615 Flycatching rate
Setting range: 1
~
100
Mfr’s value: 20
It is used to select the rotation velocity Flycatching when the rotation tracking restart mode is
adopted. The larger the parameter is, the faster the Flycatching is. If this parameter is too large,
its likely to result in unreliable tracking.
When F619=0, the function is not valid. When F619
≠
0, the function is valid. When
Flycatching time is longer than the setting value of F619, it will trip into FL.
This function code is used to limit the searching current and output current when Flycatching.
When F622=0, fixed duty ratio is valid. When bus-line voltage reaches energy consumption
brake point set by F611, braking module will start dynamic braking according to F612.
When F622=1, auto duty ratio is valid. When bus-line voltage reaches dynamic braking
threshold set by F611, braking module will start dynamic braking according to duty ratio which is
adjusted by the bus-line voltage. The higher bus-line voltage is, the greater duty ratio is, and the
better braking effect is. The braking resistor will get hotter.
F631 VDC adjustment selection
0: invalid
1: valid
2: reserved
Subject to
inverter model
F632 Target voltage of VDC adjustor (V) Setting range: 200~800
When F631=1, VDC adjustment function is valid. During motor running process, the PN bus
voltage will rise suddenly because of load mutation, over-voltage protection will occur. VDC
adjustment is used to control voltage steady by adjusting output frequency or reducing braking
torque.
If the DC bus voltage is higher than the setting value of F632, VDC adjustor will automatically
adjust the bus voltage same as the value of F632.
VDC adjustment is invalid when F106=6.
F650 High-frequency performance
Setting range:
0: Invalid
1: Terminal enabled
2: Enabled mode 1
3: Enabled mode 2
Mfr’s value: 2
F651 Switchover frequency 1
Setting range: F652-150.00
Mfr’s value: 100.0
F652 Switchover frequency 2
Setting range: 0-F651
Mfr’s value: 95.00
F619 Flycatching fault timeout period
Setting range: 0.0~3000.0S
Mfr’s value:
60.0s
F627 Current limiting when Flycatching 50-200
100
F622 Dynamic braking mode
Setting range:
0: Fixed duty ratio
1: Auto duty ratio
Mfr’s value: 1