15-14
Parameter Reference
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
F741
Analog Disconnected Protection
0: Invalid
1: Stop and AErr displays.
2: Stop and AErr is not displayed.
3: Inverter runs at the min frequency.
4: Reserved.
0
√
F742
Threshold of Analog Disconnected
Protection (%)
1~100
50
○
F745
Threshold of Pre-alarm Overheat (%)
0~100
80
○*
F747
Carrier Frequency Auto-adjusting
0: Invalid 1: Valid
1
√
F754
Zero-current Threshold (%)
0~200
5
╳
F755
Duration time of zero-current
0~60
0.5
√
15.8 Motor parameters: F800-F830
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
F800
Motor’s Parameters Selection
Setting range:
0: Invalid;
1: Rotating tuning.;
2: Stationary tuning
0
╳
F801
Rated Power
0.2
~
1000kW
○╳
F802
Rated Voltage
1
~
440V
○╳
F803
Rated Current
0.1
~
6500A
○╳
F804
Number of Motor Poles
2
~
100
4
○△
F805
Rated Rotary Speed
1
~
30000
○╳
F806
Stator Resistance Ω
0.001
~
65.53Ω (for 22kw and below
22kw)
0.1~6553mΩ (For above 22kw)
Subject to
inverter
model
○╳
F807
Rotor Resistance Ω
0.001
~
65.53
Ω
(for 22kw and below
22kw)
0.1~6553mΩ (For above 22kw)
Subject to
inverter
model
○╳
F808
Leakage Inductance(mH)
0.01
~
655.3mH (for 22kw and below
22kw)
0.001~65.53mH (for above 22kw)
Subject to
inverter
model
○╳
F809
Mutual Inductance(mH)
0.01
~
655.3mH (for 22kw and below
22kw)
0.001~65.53mH (for above 22kw)
Subject to
inverter
model
○╳
F810
Motor Rated Frequency
1.00~590Hz
50.00
○╳
F812
Pre-exciting Time
0.000
~
30.00S
0.30
√
F813
Rotary Speed Loop KP1
0.01
~
20.00 (for 22kw and below
22kw)
1~100 (For above 22kw)
Subject to
inverter
model
○
√