The Default Applications
13-7
AC10 Inverter
This is ideal for applications requiring multiple discrete speed levels.
The set-point is selected from either the sum of the analogue inputs, or as one of up to eight
other pre-defined speed levels. These are selected using DI2, DI3 and DI4, refer to the Truth
Table below.
Preset Speed Truth Table
Preset Select 1
Preset Select 2
Preset Select 3
DI4
DI3
DI2
Preset
0V
0V
0V
1
0V
0V
24V
2
0V
24V
0V
3
0V
24V
24V
4
24V
0V
0V
5
24V
0V
24V
6
24V
24V
0V
7
24V
24V
24V
8
Function setting
Setting value
F228 Macro selecting
3: Preset Speeds
F106 Control mode
2: VF control
F203 Main frequency source X
4: multi-stage speed control
F204 Accessorial frequency source Y
1: AI1
F207 Frequency source selecting
1: X+Y
F316 DI1 terminal function setting
56: manual running
F317 DI2 terminal function setting
3: mutiple stage speed 1
F318 DI3 terminal function setting
4: mutiple stage speed 2
F319 DI4 terminal function setting
5: mutiple stage speed 3
F320 DI5 terminal function setting
8: free stop
F431 AO1 analog output signal selecting
0: running frequency
Coast stop
1
2
3
5
6
4
7
8
9
10
11
12
13
14
15
16
17
18
TA
TB
TC
1
DO
24
V
CM
DI1
DI2
DI3
DI4
DI5
10
V
1
AI
2
AI
GND
1
AO
A
+
B
-
REF
Run forward
Speed trim
not used
not used
Analog output F 431=0 , running
frequency is output
.
GND
Speed trim AI2 input 4-20 mA
Speed setpoint AI 1 input 0-10V
10V
Coast stop
Preset select 1
Auto run
CM
24V
not used
Relay output
See truth table below
F 300=1 , inverter outputs
fault signal.
See truth table below
Preset select 2
Preset select 3
See truth table below
Preset select 1
Preset select 2
Preset select 3