AC10 Inverter
b) Markings for proper wiring connections;
c) “Maximum surrounding air temperature 40oC” or equivalent;
d) “Solid state motor overload protection reacts when reaches 150% of FLA” or
equivalent;
e) “Install device in pollution degree 2 environment.” Or equivalent;
f) “Suitable for use on a circuit capable of delivering not more than 5,000 rms
symmetrical amperes, 480/240 volts maximum when protected by made by COOPER
BUSSMANN LLC Class T Fuse.” Or equivalent. Recommended input fuse selection
listed below:
Frame Size or Model
Fuse Model
Fuse Current Rating
10G-31-0015-XX
10G-31-0025-XX
10G-31-0035-XX
10G-31-0045-XX
JJS-15
15A
10G-32-0050-XX
10G-32-0070-XX
10G-32-0100-XX
JJS-25
25A
10G-11-0015-XX
10G-11-0025-XX
10G-11-0035-XX
10G-11-0045-XX
JJS-15
15A
10G-12-0050-XX
10G-12-0070-XX
10G-12-0010-XX
JJS-25
25A
10G-41-0006-XX
10G-41-0010-XX
10G-41-0015-XX
JJS-6
6A
10G-42-0020-XX
10G-42-0030-XX
10G-42-0040-XX
10G-42-0065-XX
JJS-15
15A
10G-43-0080-XX
10G-43-0090-XX
10G-43-0120-XX
JJS-30
30A
10G-44-0170-XX
JJS-45
45A
10G-44-0230-XX
JJS-60
60A
10G-45-0320-XX
JJS-80
80A
10G-45-0380-XX
JJS-90
90A
10G-45-0440-XX
JJS-100
100A
10G-46-0600-XX
AJT-125
125A
10G-47-0750-XX
AJT-150
150A
10G-47-0900-XX
AJT-200
200A
10G-48-1100-XX
AJT-200
200A
10G-48-1500-XX
AJT-300
300A
10G-49-1800-XX
AJT-350
350A
10G-49-2200-XX
AJT-400
400A
10G-410-2650-XX
AJT-500
500A
10G-411-3200-XX
AJT-600
600A
10G-411-3600-XX
AJT-600
600A