Function Parameters
9-17
AC10 Inverter
·
F228 can be set to Mfr’s value by F160=1.
9.3 Multifunctional Input and Output Terminals
9.3.1 Digital multifunctional output terminals
F300 Relay token output
Setting range: 0~40
Refer to
Table 9-2 for detailed instructions.
Mfr’s value: 1
F301 DO1 token output
Mfr’s value: 14
F302 DO2 token output
Mfr’s value: 5
Table 9-2 Instructions for digital multifunctional output terminal
Value Function
Instructions
0
No function
Output terminal has no functions.
1
Inverter fault protection
When inverter trips this signal is output high.
2
Over latent frequency 1
Please refer to instructions from F307 to F309.
3
Over latent frequency 2
Please refer to instructions from F307 to F309.
4
Free stop
Under free stop status, after stop command is
given, ON signal is output until inverter
completely stops.
5
In running status 1
Indicating that inverter is running and ON signal
is output.
6
DC braking
Indicating that inverter is in the status of DC braking
and ON signal is output.
7
Acceleration/deceleration time
switchover
Indicating that inverter is in the status of
acceleration/deceleration time switchover
8
Reserved
9
Reserved
10
Inverter overload pre-alarm
Stall Warning
After inverter overloads, ON signal is output after
the half time of protection timed, ON signal stops
outputting after overload stops or overload
protection occurs.
F228 Application selection
Setting range:
0: Invalid
1: Basic speed control
2: Auto/manual speed control
3: Preset speed control
4: Terminal speed control
5: PID control
Mfr’s value: 0