34
COMMUNICATION SETUP
The procedures described below let you set the parame-
ters for the Disk Recorder to communicate with external
devices.
PS.Data Setup
These items let you set the parameters for communication
between the System Controllers and the Disk Recorders
when the system is controlled with the PS.Data mode
(Panasonic Security Data).
1. Click the PS.Data SETUP in the WJ-HD500 SETUP
MENU window.
The PS.Data SETUP window as shown in the figure will
appear on the display.
2. Select an item parameter in the window.
3. To return to the previous setup menu, click the HD500
SETUP MENU in the underneath of window.
Or to open the further divided setup window, click the
CAMERA NUMBER SETUP display in the underneath of
the window
■
PS.Data Setup
The described below let you set the communication para-
meters for RS-485 communication.
1. Select a unit address number (001 - 099) of the Disk
recorder to be used for RS-485 communication by
pressing the keyboard.
The factory default setting is 001.
2. Select a transmission speed (Baud Rate) by clicking
the pulldown list.
The factory default setting is 9600 bps.
3. Select NONE, EVEN or ODD for parity check by clicking
the button.
The factory default setting is NONE.
4. Select either 1 or 2 for the number of stop bits by click-
ing the button.
The factory default setting is 1 bit.
5. Select OFF, 100, 200, 400, 1 000 ms for the wait time by
clicking the pulldown list.
The item lets you set the waiting time in milliseconds
(ms) to retry after confirming that no data is received
from the controller for RS-485 communication.
When no transmission is needed, select OFF.
The factory default setting is OFF (no retry).
6. Select a mode of the alarm notification by clicking the
pulldown list.
The item lets you enable or disable notification of the
alarm data received to the controller (Unit Number 1).
OFF:
Select this parameter if the system controller is
not connected to the system.
0(SEC):
Each time an alarm is received, it is transmitted
to the system controller.
1(SEC):
The received alarm is stored for 1 second, and
that data is sent to the system controller.
5(SEC):
The received alarm is stored for 5 seconds,
and that data is sent to the system controller.
The factory default setting is 1(SEC).
7. Click the
[SET]
button to execute the selections.
2400bps 4800bps 9600bps
38400bps 19200bps
Summary of Contents for WJ-HDB502
Page 7: ...7 WJ HDB502 BOARD SETUP ...
Page 13: ...13 WJ HD500 SETUP ...
Page 38: ...39 SYSTEM OPERATIONS ...