№
SR-ZSV00039
-
56
-
Motor Business Unit, Appliances Company, Panasonic Corporation
6
-
4
-
4
Emergency Stop at Alarm
If an alarm occurs that requires an immediate stop, setting the following parameters will control the motor to
immediately stop it.
(1) Related parameters
Category
No.
Parameter
Setup range
Unit
Function
5
10
Sequence at alarm
0
7
To set up the states during the deceleration and after the stop when
an alarm occurs.
The immediate stop is valid when the parameter is set to either 4, 5,
6 or 7.
5
11
Torque setup for
emergency stop
0
500
%
To set a torque limit for the immediate stop.
5
13
Overspeed level
0
20000
r/min
If the motor speed exceeds the value set with this parameter, Err26.0
“Over-speed protection” occurs.
If the value is set to 0, the overspeed level will be set at the
maximum number of motor revolution multiplied by 1.2.
6
14
Emergency stop time at
alarm
0
1000
ms
To set the allowable time for the immediate stop to complete when
there is an alarm. The time exceeding the value set for this
parameter will force a state of alarm.
If 0 is set for this parameter, the immediate stop doesn’t do, and
become an alarm state immediately.
6
15
2
nd
over-speed level
setup
0
20000
r/min
If the motor speed exceeds the value set for this parameter during an
immediate stop which has been caused by an alarm, Err26.1 “2
nd
over-speed protection” will occur.
If the value is set to 0, the overspeed level will be set at the
maximum number of motor revolution multiplied by 1.2.
(2) Item
Immediate stop operation when an alarm requiring an immediate stop occurs
(Note) To protect against runaway upon instantaneous stopping, specify an allowable excessive speed level in
Pr6.15 “2
nd
over-speed level setup”. If 2
nd
excessive speed protection, which is an error not applicable to
instantaneous stopping, is activated, it immediately leads to error tripping. However, if set lower than
Pr5.13 “Over-speed level setup”, a fast shutdown will not be executed due to Err26.1 “2
nd
over-speed
protection” that occurs before Err26.0 “Over-speed protection”.
If Err26.0 and Err26.1 are detected at the same time, Err26.0 will be displayed but a fast shutdown will
not be executed due to Err26.1 that is internally occurring.
Torque limit
Speed
[r/mn]
Time
Alarm state (operation after stop
:
DB/free-run)
Immediate stop
operation
Normal operation
(per commands from the controller)
Motor speed
Pr5.11
For normal operation
For normal operation
Alarm requiring immediate stop has occured
No alarm has occured
Alarm
Speed crite-
ria to stop
(30r/min
If the time specified by P
r
6.14 “
Emergency stop time at alarm
” has passed since an
alarm requiring an immediate stop had occurred and if the actual speed is over 30
r/min, then an alarm state will be prompted immediately. An alarm not applicable
to instantaneous stopping in the drive during a fast shutdown immediately leads to
alarm state.
Immediate stop time
*
*P
r
5.11 “
Torque setup for emergency stop
” to alleviate shock caused
by immediate stop