№
SR-ZSV00039
-
7
-
Motor Business Unit, Appliances Company, Panasonic Corporation
Function number table
Setting
Signal
Code
a connect
b connect
Invalid
-
00h
Not available
Positive overtravel limit
POT
01h
81h
Negative overtravel limit
NOT
02h
82h
Servo on
SRV-ON
03h
83h
Alarm clear
A-CLR
04h
Not available
(
No setting
)
-
05h
85h
Gain switch
GAIN
06h
86h
Deviation counter clear
CL
07h
Not available
Command pulse inhibition
INH
08h
88h
Torque limit switch
TL-SEL
09h
89h
Damping switch 1
VS-SEL1
0Ah
8Ah
Damping switch 2
VS-SEL2
0Bh
8Bh
Command scaling switch
DIV1
0Ch
8Ch
Command scaling switch 2
DIV2
0Dh
8Dh
(
No setting
)
-
0Eh~13h
8Eh~93h
Forced alarm input
E-STOP
14h
94h
(
No setting
)
-
15h
95h
Precautions:
・
Do not set any value other than set values specified in the table.
。
If it is set other than values specified in the
table,
Err33.2 "IF input function number error 1 protection" or Err33.3 "IF input function number error 2 protection" will occur.
And the (No setting) in the table is set to protection function. Because input do not operate, please set it to invalid(00h).
・
A function can not be assigned to more than one signal. If any function is assigned to more than one signal, Err33.0 "IF overlaps
allocation error 1 protection" and Err33.1 "IF overlaps allocation error 2 protection" will occur.
・
Deviation Counter Clear (CL) can be assigned only to SI7 Input. If it is assigned to the other signals, Err33.6 "CL fitting error
protection" will occur.
・
Command Pulse Inhibition (INH) can be assigned only to SI10 Input. If it is assigned to the others, Err33.7 "INH fitting error
protection" will occur.
・
Control input pins set as invalid do not affect operations.
・
Servo-on Input Signal (SRV-ON) must always be assigned. When it is not assigned, Servo-on cannot be activated