Operating instructions for Pool control-40.net filter control unit
Page: 8 (34)
must be set for the speeds N1, N2 and N3.
Connecting the power supply for a Zodiac FloPro VS pump
A Zodiac FloPro VS pump can be connected directly to the PC-40
unit. Connect the speed controller to terminals 6-13.
A separate mains power supply must be provided for the pump. The
power supply cannot be provided by the PC-40.
There must be a link inserted between the two WSK terminals
(winding protection switch).
The option Filter pump - type: var. speed pump must be selected for
the filter pump in the configuration menu.
Always refer to the operating instructions for the pump.
At the pump, the speed controller must be connected to the
designated terminals on the back of the user interface. The speeds
required for ECO mode (level 1), normal mode (level 2) and
backwash mode (level 3) must be assigned to speed levels 1 to 3.
Connecting the power supply for a Pentair IntelliFlo pump
An IntelliFlo pump can be controlled by the PC-40 using the Pentair
Intellicom controller.
A separate mains power supply must be provided for the pump. The
power supply cannot be provided by the PC-40.
There must be a link inserted between the two WSK terminals
(winding protection switch).
The option Filter pump - type: var. speed pump must be selected for
the filter pump in the configuration menu.
Always refer to the operating instructions for the pump.
Connecting the power supply for a Pentair SuperFlo VS pump
A SuperFlo VS pump can be controlled by the
PC-40 unit.
A separate mains power supply must be provided
for the pump. The power supply cannot be provided
by the PC-40.
There must be a link inserted between the two
WSK terminals (winding protection switch).
The option Filter pump - type: var. speed pump
must be selected for the filter pump in the
configuration menu.
Always refer to the operating instructions for the
pump.