Error and Alarm Processing
Section 5-1
5-1-3
Alarms Detected by the Temperature Control Unit
The ERC Indicator will light when an alarm occurs that is detected by the
Temperature Control Unit itself. The corresponding error flag will be turned
ON in the Unit’s Special I/O Unit Area. A separate CIO word is allocated to
each loop, as shown in the following table.
ERC Indicator Lit and RUN Indicator Lit
These alarms indicate that an incorrect operation was performed while the Unit
was operating normally. These alarms are cleared automatically when the
cause of the alarm is corrected.
If pin 1 of the Temperature Control Unit’s DIP Switch is OFF (stop operation
when CPU Unit is in PROGRAM mode), the RUN Indicator will be OFF when
the CPU Unit is in PROGRAM mode.I
Bit
CIO word
n+8
n+9
n+18
n+19
15
Loop 1
status
Save Completed
Loop 2
status
Save Completed
Loop 3
status
Save Completed
Loop 4
status
Save Completed
14
Sensor Error
Sensor Error
Sensor Error
Sensor Error
13
CT Overflow
CT Overflow
0
0
12
Fatal Control Error
Fatal Control Error
Fatal Control Error
Fatal Control Error
11
Standby
Standby
Standby
Standby
10
PID Constants
Calculated
PID Constants
Calculated
PID Constants
Calculated
PID Constants
Calculated
09
Setting Error
Setting Error
Setting Error
Setting Error
08
Stop
Stop
Stop
Stop
07
0
0
0
0
06
0
0
0
0
05
0
0
0
0
04
Control Output
Control Output
Control Output
Control Output
03
AT
AT
AT
AT
02
HB
HB
0
0
01
AL1
AL1
AL1
AL1
00
AL2
AL2
AL2
AL2
Lit
RUN
ERC
ERH
Not lit
Bit
Alarm name
Cause
Control status
Processing
Bit 14
Sensor Error
An input error has
occurred.
Control operation continues.
(Output OFF.)
Alarm operates as if the tem-
perature is out of range.
Check the corresponding loop for incor-
rect input wiring, short circuit, and incor-
rect input type setting.
Bit 13
CT Overflow
The heater current
is above 55.0 A.
Control operation continues.
The corresponding loop’s heater current
value will be correct when the current is
within range.
Bit 09
Setting Error
There is an error in
a setting.
The incorrect setting will be
ignored and operation will
continue with the settings
retained in the Unit.
Check the corresponding loop’s “Setting
Error Number” in CIO (n+7) or
CIO (n+17). Correct the indicated setting.
Bit 02
Heater Burnout A heater circuit has
burned out.
Control operation continues.
Check the corresponding loop’s heater
and repair the heater where the burnout
occurred.
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......