41
Data Exchange with the CPU Unit
Section 2-5
Two-loop Units
I/O
Address
Loop
Name
Function
Word
Bits
Outputs
(CPU Unit
to Tem-
perature
Control
Unit)
n
00 to 15 Loop 1 Set Point
Set the Set Point for the loop as 4-digit BCD or 16-bit binary.
For negative BCD values, set the most significant digit to F.
The values set here are transferred to RAM.
n+1
00 to 15 Loop 2 Set Point
n+2
15
Loop 1 Save Bit
Operating Parameters are written from RAM to EEPROM in the
Temperature Control Unit when a Save Bit is turned ON. Refer to
2-6 Data Ranges
for a list of the specific parameters that are writ-
ten.
DO NOT turn OFF the power supply when data is being written
from RAM to EEPROM. Confirm that the Save Completed Flag
has turned ON before turning OFF the power supply.
14
Loop 2 Save Bit
13
Loop 1 Change PID
Constants Bit
When a Change PID Constants Bit is turned ON, the correspond-
ing PID Constants Calculated Flag will turn OFF and the PID con-
stants stored as Operating Parameters will be retransferred to the
Temperature Control Unit.
12
Loop 2 Change PID
Constants Bit
08 to 11 ---
---
Leave set to all zeros.
7
---
---
Leave set to 0.
6
Loop 1 Stop Bit
Turn OFF the Stop Bit to perform temperature control for loop 1
and turn it ON to stop temperature control for loop 1.
The Stop Bit will not function if pin 1 on the DIP switch is OFF and
the CPU Unit is in PROGRAM mode.
5
---
---
Leave set to 0.
4
Loop 2 Stop Bit
Turn OFF the Stop Bit to perform temperature control for loop 2
and turn it ON to stop temperature control for loop 2.
The Stop Bit will not function if pin 1 on the DIP switch is OFF and
the CPU Unit is in PROGRAM mode.
3
Loop 1 Stop AT Bit
Turn ON the Stop AT Bit to stop autotuning for loop 1. The status of
the Stop AT Bit is ignored if autotuning is not being performed.
2
Loop 1 Start AT Bit
Turn ON the Start AT Bit to start autotuning for loop 1. The status
of the Stop AT Bit is ignored if the Stop AT Bit for loop 1 is ON.
1
Loop 2 Stop AT Bit
Turn ON the Stop AT Bit to stop autotuning for loop 2. The status of
the Stop AT Bit is ignored if autotuning is not being performed.
0
Loop 2 Start AT Bit
Turn ON the Start AT Bit to start autotuning for loop 2. The status
of the Stop AT Bit is ignored if the Stop AT Bit for loop 2 is ON.
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......