23
Part Names and Functions
Section 2-3
2-3-4
DIP Switch Setting Functions
ON is to the right.
Operation in PROGRAM
mode (Pin 1)
The following table shows how the Temperature Control Unit will operate
when the CPU Unit’s operating mode is changed.
Temperature Units (Pin 2)
Select either
°
C display (centigrade) or
°
F display (farenheit). When
°
F is
selected, the temperature is converted using the following equation:
°
F = (
°
C
×
1.8) + 32
Data Format (Pin 3)
Pin 3 selects whether the data exchanged between the Temperature Control
Unit and CPU Unit is handled as 4-digit BCD or binary (i.e., 4-digit hexadeci-
mal.) This switch setting controls the data format for the various settings such
as SPs, PVs, alarm settings in both the CIO and DM Areas.
Note
If BCD format is selected, it isn’t necessary to convert the data (Binary to BCD
conversion) in the program when displaying the actual temperature so the lad-
der program load can be reduced. However, parts of some temperature
ranges cannot be displayed in BCD so it will be necessary to use the binary
format in those cases.
Pin
Function
ON
OFF
Factory
setting
1
Operation when CPU Unit is in
PROGRAM mode
Continue
Stop
OFF
2
Temperature units (
°
C/
°
F)
°
F
°
C
3
Data format
16-bit binary
4-digit BCD
4
Control operation (loops 1 and 3) Forward
(cooling)
Reverse
(heating)
5
Control operation (loops 2 and 4) Forward
(cooling)
Reverse
(heating)
6
Control method
ON/OFF control PID control
7
Initialize settings in EEPROM
Initialize
Do not initialize
8
Transfer settings in EEPROM
Transfer
Do not transfer ON
1
2
3
456
7
8
MODE
Temperature Control Unit
settings
Operation of Temperature Control Unit when CPU
Unit’s operating mode is changed
Pin 1
Stop Bit
From RUN or MONITOR
to PROGRAM
From PROGRAM
to RUN or MONITOR
OFF (Stop)
Run
Stop operation
Continue operation
Stop
Stop operation
Stop operation
ON (Continue) Run
Continue operation
Continue operation
Stop
Stop operation
Stop operation
Pin 3 setting
Data format
Example
(SP:
−
200 to 1,300
°
C)
ON
Binary (4-digit Hexadecimal)
FF38 to FFFF to 0514
(
−
200 to
−
1 to 1,300)
OFF
4-digit BCD
F200 to 1300
(
−
200 to 1,300)
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......