10
Comparison to C200H Temperature Control Units
Section 1-3
1-3
Comparison to C200H Temperature Control Units
Item
CJ-series Temperature Control Units
C200H Temperature Control Units
Model number
CJ1W-TC00
@
/10
@
C200H-TC00
@
/10
@
Unit type
CJ-series Special I/O Unit
C200H Special I/O Unit
Compatible PLCs
CJ-series PLCs
CS-series, C200HX/HG/HE, C200HS,
and C200H PLCs
Number of control loops
2 loops (with heater burnout detection)
or 4 loops
2 loops
Allocated I/O words
20 words (6 output and 14 input)
10 words (3 output and 7 input)
Control inputs
Thermocouple (R, S, K, J, T, B, or L) or
platinum resistance thermometers
(JPt100 or Pt100)
Thermocouple (R, S, K, J, T, E, B, N, L,
or U) or platinum resistance thermome-
ters (JPt100 or Pt100)
Control modes
PID control or ON/OFF control
(PID control features two degrees of freedom and autotuning.)
Control outputs
CJ1W-TC
@
01/
@
03:
Open collector NPN outputs (pulse),
external 24-VDC power supply
CJ1W-TC
@
02/
@
04:
Open collector PNP outputs (pulse),
external 24-VDC power supply
C200H-TC
@
01:
Open collector NPN outputs (pulse),
external 24-VDC power supply
C200H-TC
@
02:
Voltage outputs (pulse), 12-VDC outputs
C200H-TC
@
03:
Current outputs (linear), 4 to 20 mA DC
Setting accuracy,
indicator accuracy
Thermocouple
input
±0.3% or ±1
°
C (whichever is larger) ± 1
digit max.
±0.5% or ±2
°
C (whichever is larger) ± 1
digit max.
Platinum resis-
tance ther-
mometer input
±0.3% or ±0.8
°
C (whichever is larger)
± 1 digit max.
±0.5% or ±1
°
C (whichever is larger) ± 1
digit max.
Storage/display data format for data
exchanged with CPU Unit
BCD or binary (selectable)
BCD only
RUN/STOP control
Supported (Controlled from the CPU Unit through a bit allocated in the Special I/O
Unit area.)
Operation when CPU Unit is in PRO-
GRAM mode
The Temperature Control Unit can be set to continue operating or stop operating
when the CPU Unit is in PROGRAM mode. (Selectable)
Auto/Manual switch for operational
output
Not supported.
Autotuning (AT) of PID constant
Can be started and stopped from the
CPU Unit through bits allocated in the
Special I/O Unit area.
Can be started and stopped from the
CPU Unit through bits allocated in the I/
O Unit area or from the Data Setting
Console.
Sampling period
500 ms
Input compensation value
−
99.9 to 999.9
°
C or
°
F
Data setting banks
None
8 banks max.
Output wiring method
Terminal block
Connector
Data Setting Console
Not supported (Cannot be used.)
Supported (Can be used.)
Heater Burnout Detection
Yes (Two-loop Units only)
Yes
CT heater detection current
0.0 to 50.0 A
0.0 to 5.0 A
SV write memory
EEPROM (100,000 writes) or RAM
Effect on the CPU Unit’s cycle time
0.4 ms
2.6 ms
CPU Unit’s required cycle time
Unrestricted
Restricted (8 ms minimum cycle time)
Dimensions
90
×
31
×
65 mm (H
×
W
×
D)
130
×
34.5
×
120.5 mm (H
×
W
×
D)
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......