14
Specifications
Section 2-1
Note
1.
The last three digits of the model number indicate the Unit’s features:
2.
Indication accuracy of thermocouples
• Accuracy ratings are given for the Temperature Control Unit used in a
set with a cold-junction compensator (on the terminal block). Always
use the Unit and terminal block in a set. There are labels with serial
numbers attached to the terminal blocks and Units to help keep track
of the sets.
• When returning a thermocouple-type Temperature Control Unit for re-
pair, always return the Unit and the terminal block (with the cold-junc-
tion compensator) as a set.
Heater Burnout (HB)
Alarm
Note
If the control output is ON for less than 200 ms, the heater burnout detection
function will not operate and heater current measurement will not be per-
formed.
Current Transformer
(CT) Ratings
External terminal
connections
Removable terminal block with 18 points (M3 screws)
Effect on the CPU
Unit’s cycle time
0.4 ms
Item
Specification
CJ1W-TC
@
0
@
Output type
Always 0.
Input type
0: Thermocouple input
1: Platinum resistance thermometer input
1: NPN outputs, four-loop control outputs
2: PNP outputs, four-loop control outputs
3: NPN outputs, two-loop control outputs and heater
burnout alarm outputs
4: PNP outputs, two-loop control outputs and heater
burnout alarm outputs
Item
Specification
Maximum heater current
Single-phase AC, 50 A
Indication accuracy of input cur-
rent
±5% of full scale ± 1 digit max.
Heater burnout alarm setting
range
0.1 to 49.9 A (0.1 A units)
The heater burnout detection function will not
operate if the set value is set to 0.0 A or 50.0 A.
(When the SV is 0.0 A, the heather burnout alarm
will be OFF. When the SV is 50.0 A, the heater
burnout alarm will be ON.)
Min. detectable ON time
(See note.)
200 ms
Item
E54-CT1
E54-CT3
Max. continuous heater current
50 A
120 A (See note 1.)
Dielectric strength
1,000 VAC (1 min.)
Vibration resistance
50 Hz, 98 m/s
2
Weight
Approx. 11.5 g
Approx. 50 g
Accessories
None
Contacts (2)
Plugs (2)
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...